Eingeschränkt.
RSP specification for mv smart line sectionalizer
Sonstiges
English
This PDF is SEC’s utility‑grade technical specification for pole‑mounted smart line sectionalizer, for EPCs, bidders and design institutes for tender submission, gap analysis and pre‑award review. It follows IEC 62271‑103, ANSI C37.63, IEC 60870‑5, IEC 61850 and SEC requirements. Ratings: 13.8‑36 kV, 400A continuous current, 10kA‑3s short‑time withstand; adjustable 16‑640A phase‑fault, 3.5‑320A earth‑fault, 1‑3 configurable trip counts. Equipped with vacuum/SF6 interruption, sealed stainless‑ste