占位边距

SF6-Free Switchgear / Ring Main Unit for Urban Distribution Networks-12kV

  • SF6-Free Switchgear / Ring Main Unit for Urban Distribution Networks-12kV

Key attributes

Brand ROCKWILL
Model NO. SF6-Free Switchgear / Ring Main Unit for Urban Distribution Networks-12kV
Rated voltage 12kV
Rated frequency 50/60Hz
Series XGN

Description

This sealed air-insulated ring main unit enables dual-circuit distribution with SF₆-free technology. Air at atmospheric pressure in a sealed enclosure delivers reliable insulation without gas monitoring or leakage risk. The dual-circuit configuration supports independent loop supply with automatic fault isolation.

Integrated load break and earthing switches provide safe switching and visible isolation for urban substations, industrial parks, and commercial complexes.

Key Features

  • SF₆-Free Eco Design:Clean air at normal pressure as insulating medium. Zero GWP, no gas monitoring, no leakage risk.
  • Fully Sealed Enclosure:Hermetically sealed stainless steel tank, protection IP67, prevents moisture/dust/vermin ingress.
  • Dual-Circuit Redundancy:Two independent load break switches for dual-loop supply with automatic fault isolation and self-healing restoration.
  • Maintenance-Free Operation:No gas refilling, no periodic cleaning, mechanical endurance ≥5000 operations.

Parameters

Name

Unit

Parameter Value

Rated Voltage (Ur)

kV

12

Rated Frequency (fr)

Hz

50/60

Rated Current (Ir)

A

630

Short - time Power Frequency Withstand Voltage (Ud)

Between Fractures

kV

48

Between Phases

kV

42

Phase to Ground

kV

42

Lightning Impulse Withstand Voltage (Up)

Between Fractures

kV

95

Between Phases

kV

75

Phase to Ground

kV

75

Rated Short - time Withstand Current (Ik)

kA

20/25

Rated Short - circuit Duration (tk)

s

4

Rated Peak Withstand Current (Ip)

kA

50/63

Rated Short - circuit Breaking Current (Isc)

kA

20/25

Rated Short - circuit Making Current (Ima)

 

Vacuum Interrupter

kA

50/63

Earthing Switch

   

Auxiliary Circuit and Control Circuit

Rated Voltage (Ua) DC/AC

V

<400

Power Frequency Withstand Voltage (1min)

V

2000

Mechanical Life

 

Circuit Breaker

Times

10000

Disconnecting Switch

Times

3000

Earthing Switch

Times

3000

Electrical Life  

Circuit Breaker

Class

E2

Earthing Switch

Class

E2

Protection Grade of Cabinet Enclosure

 

IP4X

Protection Grade of Sealed Box

 

IP65

 Environmental Conditions

Ambient Temperature (Max / 24h Avg / Min) +40 °C / ≤+35 °C / -25 °C
Altitude ≤ 1000 m
Relative Humidity (Max at 25°C / Max at 40°C) 95% / 50%
Water Vapor Pressure (Max / Min) 2.2 kPa / 0.1 kPa
Solar Radiation ≤ 1000 W/m²
Pollution Class Class II

Solutions for Ring Main Unit

  • Rockwill's SF6 Circuit Breaker Solution for 33kV Substations in Nigeria
    Project BackgroundNigeria’s tropical climate, characterized by year-round high temperatures (annual average of 35°C) and humidity (≥80%), poses significant challenges to the sealing integrity, insulation performance, and gas management of electrical equipment. Rockwill was contracted to upgrade a 33kV substation, deploying its proprietary HV-type SF6 circuit breaker to address critical issues: Sealing Failure Risks: Accelerated aging of seals due to heat and water ingres

FAQ for Ring Main Unit

In which scenarios are environmentally friendly cabinets commonly used? (e.g., urban distribution network, industrial park)
They are widely used in urban distribution networks, new residential communities, industrial parks, data centers, airports, railways, and alpine/humid coastal areas. They are especially suitable for environmentally sensitive areas (e.g., scenic spots, ecological reserves) and projects with strict environmental protection requirements (e.g., green buildings, low-carbon industrial parks) due to their eco-friendly characteristics.
Do environmentally friendly cabinets have self-healing ability after insulation breakdown?
Gas-insulated environmentally friendly cabinets have certain self-healing ability. When insulation breakdown occurs due to transient overvoltage, the insulating gas (dry air, N2) molecules can recombine to restore insulation performance after the fault is removed, without permanent damage. However, solid-insulated eco-friendly cabinets do not have self-healing ability; insulation breakdown will cause permanent damage and require component replacement.
Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Message
Inquiry
WhatsApp
WhatsApp
Chat
Chen/CEO