Customizable SF6 Ring Main Unit for ring main power supply-12kV

  • Customizable SF6 Ring Main Unit for ring main power supply-12kV

Key attributes

Brand ROCKWILL
Model NO. Customizable SF6 Ring Main Unit for ring main power supply-12kV
Rated voltage 12kV
Rated frequency 50/60Hz
Series XGN

Description

The XGN15-12 is a 12kV-class SF₆-insulated ring main unit (RMU) designed for secondary distribution networks. Sealed stainless steel enclosure with SF₆ gas insulation protects against moisture, pollution, corrosive atmospheres, and dust. Rated at 630A with a short-circuit making capacity of 50kA, it supports ring main and radial configurations for industrial, commercial, and residential applications.

The unit is equipped with SF₆ switch-disconnectors or switch-fuse combinations, capable of making and breaking rated load current, making rated short-circuit current, and interrupting transformer no-load current. When combined with a fuse, the unit can interrupt 31.5kA short-circuit current, providing full system control and protection.

Key Features

  • Sealed tank construction: All live parts enclosed in SF₆ gas-no exposure to moisture, dust, or corrosive gases

  • Plug-in solid busbars: Between-unit connections via insulated plug-in busbars, eliminating exposed conductors

  • External resin-cast fuses: Single-phase fuses mounted outside the enclosure, preventing phase-to-phase faults

  • Modular design: Single-cabinet fully-enclosed construction, factory or site configurable

  • Compact footprint: 375mm (W) ×1400mm (H)×980mm (D)

  • CNC-fabricated cabinet: Aluminum-zinc coated steel plates, riveted construction for airtightness

  • Maintenance-free design: No on-site SF₆ filling required during service life

Parameters 

Parameter Unit Value
Rated Voltage (Ur) kV 12
Rated Frequency Hz 50/60
Rated Current (busbar) A 630
Rated Short-time Withstand Current (Ik) kA/3s 20 / 25
Rated Peak Withstand Current (Ip) kA 50 / 63
Rated Active Load Breaking Current A 630
Rated Cable Charging Breaking Current A 10
Rated Short-circuit Making Current kA 50 / 63
1min Power Frequency Withstand (phase-to-earth) kV 28
1min Power Frequency Withstand (across isolating distance) kV 32
Lightning Impulse Withstand (phase-to-earth) kV peak 75
Lightning Impulse Withstand (across isolating distance) kV peak 85
SF₆ Gas Pressure (20°C, gauge) MPa 0.15
Mechanical Endurance operations 2000
Degree of Protection (enclosure) IP IP67
Cabinet Dimensions (W×H×D) mm 375 ×1400 × 980

Working Environment Conditions

Ambient Temperature -25°C ~ +40°C
Humidity ≤95% monthly average
Altitude ≤1000m (higher options available)
Pollution Level Class II (IEC 60815)

Solutions for Ring Main Unit

  • Comparison of SF6 Gas-Insulated Ring Main Units and Solid-Insulated Ring Main Units
    IntroductionCurrently, SF6 gas-insulated ring main units (hereinafter referred to as "SF6 RMUs") dominate the market. However, SF6 gas is internationally recognized as one of the primary greenhouse gases. To achieve environmental protection and emissions reduction, its use must be reduced and restricted. The emergence of solid-insulated ring main units (RMUs) has addressed the issues associated with SF6 RMUs while incorporating numerous new features.1 Ring Mains Power Supply and Ring Main Units
  • In-depth Solutions for Common Issues in SF6 Ring Main Units (RMUs)
    In-depth Solutions for Common Issues in SF6 Ring Main Units (RMUs)The stable operation of SF6 high-voltage RMUs is critical to grid safety. Addressing typical problems exposed during long-term operation, and based on industry practices and technical specifications, the following systematic solutions are proposed:I. Comprehensive Gas Leakage Management Plan Phenomenon & Risk: SF6 gas leakage reduces dielectric strength (breakdown voltage drops by over 30% when pressure falls below 0.4MPa).
  • Analysis of Two 10kV SF₆ Ring Main Unit Failures and Live Testing
    Analysis of Two 10kV SF₆ Ring Main Unit Failures and Live Testing1 Introduction to 10kV SF₆ Ring Main UnitsA 10kV SF₆ ring main unit (RMU) typically consists of a gas tank, an operating mechanism compartment, and a cable connection compartment. Gas Tank: The most critical component, housing the load switch busbar, switch shaft, and SF₆ gas. The load switch is a three-position switch, including an isolating blade and an arc-extinguishing shield. Operating Mechanism Compartment: The operating mech
  • 10kV SF₆ Ring Main Units (RMUs) Common Fault Prevention Measures
    10kV SF₆ Ring Main Units (RMUs) Common Fault Prevention MeasuresDuring the development of urban distribution network cabling, 10kV SF₆ Ring Main Units (RMUs) (European-style), serving as ring power supply nodes, have been widely adopted due to their features such as full insulation, complete enclosure, maintenance-free operation, compact size, and flexible, convenient installation. However, as the number of RMUs in use increases, the occurrence of faults within RMUs has also gradually risen.1 Co
  • Issues and Countermeasures for 10kV SF₆ Gas-Insulated Common Tank Ring Main Unit (European-Style) Cable Connections
    Issues and Countermeasures for 10kV SF₆ Gas-Insulated Common Tank Ring Main Unit (European-Style) Cable ConnectionsWith the extensive use of cable lines in urban distribution networks, 10kV SF₆ gas-insulated common tank Ring Main Units (RMUs) (European-style) are widely adopted as network nodes due to their characteristics of full insulation, complete enclosure, maintenance-free operation, compact size, and flexible installation. These European-style SF₆ common tank RMUs are suitable for coastal

Documentation Resource Library Ring Main Unit

Rockwill Electric Group Profile
Public.
Rockwill Electric Group Profile
Brochure
English

FAQ for Ring Main Unit

How are inter-unit connections made?

Insulated plug-in busbar connectors — no exposed conductors, ensuring convenient and safe installation.

Is the XGN15-12 maintenance-free?

Yes. No on-site SF₆ gas filling required. Fully sealed structure encloses all live parts in SF₆ gas, requiring no routine maintenance.

Does the XGN15-12 support short-circuit protection with fuses?

Yes. With fuse combination, the unit can interrupt 31.5kA short-circuit current. External resin-cast fuses are mounted outside the enclosure to prevent phase-to-phase faults.

Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Message
Inquiry
WhatsApp
WhatsApp
Chat
Chen/CEO