| Brand | ROCKWILL |
| Series | RLS |
| Rated voltage | 12kV/24kV |
| Rated transferring current | 1700A/1200A |
| Rated withstand current(peak) | 80kA/63kA |
| Short time withstand current (2s) | 31.5kA/25kA |
he RLS-12/24kV indoor high-voltage g3 load switch adopts eco-friendly g3 gas as the arc-extinguishing and insulating medium, equipped with three-position integrated contacts (closed, open, earthed). It features compact size, easy installation and operation, and strong environmental adaptability.
The RLS-12/24kV indoor high-voltage g3 load switch and RLS-type g3 load switch-fuse combination are designed to control and protect power equipment in power supply systems and substations, especially applicable to ring main units, cable branch cabinets, and distribution switchgear stations.
| Rated voltage | 12kV | 24kV |
| Rated frequency | 50/60Hz | |
| Rated current | 630/800A | |
| Rated 1min power frequency withstand voltage (Dry/Wet) | 38/42/48kV | 50/60kV |
| Lightning impulse withstand voltage | 75/85kV | 125/150kV |
| Rated short circuit breaking current(peak) | 80kA | 63kA |
| Rated active load and close circuit breaking current | 63A | 50A |
| Rated transferring current | 1700A | 1200A |
| Rated short circuit making current(peak) | 80kA | 63kA |
| Rated cable(line) charging breaking current | 50 and 10A | |
| Cable charge breaking current in earthing fault | 20A | |
| Rated withstand current(peak) | 80kA | 63kA |
| Short time withstand current (2s) | 31.5kA | 25kA |
| Mechanical life | 5000/3000 times | 2000 times |
Note: If it needs to be installed in plateau areas with an altitude higher than 1,000 meters, it is essential to consult with the manufacturer to take necessary measures to strengthen insulation during the ordering process.
24kV

The RLS series uses g3 gas to cut GWP by over 99% while matching the arc-extinguishing and insulation strength of . This ensures eco-friendly operation at 12kV-36kV without increasing the equipment's physical footprint.
Q: What are the benefits of the integrated "Three-Position" contactor?
A: By combining ON, OFF, and EARTH functions into one system, RLS minimizes volume and features mechanical interlocking to prevent energized grounding. It is the ideal solution for compact Ring Main Units (RMUs).
Q: How does RLS ensure stability in extreme environments?
A: Featuring a hermetically sealed tank, RLS is immune to moisture and pollutants. The optimized g3 mixture prevents liquefaction at low temperatures, ensuring stable insulation and operational reliability in high-altitude or frigid regions.