| Brand | ROCKWILL |
| Model NO. | Solid Insulation Ring Main Unit/ distribution board-17.5kV to 24kV |
| Rated voltage | 24kV |
| Rated frequency | 50/60Hz |
| Series | RSS |
Pioneer in China's eco-friendly switchgear sector, we have specialized in R&D and manufacturing of SF₆-free switchgear for decades. With core technologies, we have established industry standards. Boasting a fully independent end-to-end production chain, we have built a product matrix of zero-emission and high-reliability eco-friendly switchgear, making us a trusted choice for power grid construction.
It is mainly composed of three functional units, namely circuit breaker unit, load switch, and combined electrical unit. Each unit can be used alone or can be freely expanded. Its structure is divided into intelligent control instrument room, operating mechanism and primary part.
The solid insulation ring main unit is a device that uses solid insulating materials as the main insulating medium. After the main conductive circuits such as conductive connection, isolating switch, grounding switch, main busbar, branch busbar, etc. are single or combined, they are encapsulated into one or several combinations or modules with solid insulating medium.
The voltage classes of some of these eco-friendly switchgears include 6kV, 6.3kV, 6.6kV, 6.9kV, 7.2kV, 10kV, 10.5kV, 11kV, 11.5kV, 12kV, 13.2kV, 13.8kV, 14.5kV, 14.4kV, 15kV, 15.5kV, 15.6kV, 17.5kV, 20kV, 21.9kV, 22kV, 24kV, 30kV, 33kV, 33.5kV, 34.5kV, 35kV, 36kV, 38kV, 38.5kV, 40.5kV, 44kV, 45kV, 46kV, 66kV and 69kV. and customization is available.
Feature
Normal use conditions
Ambient air temperature: maximum 40°C, (average value within 24 hours shall not exceed 35°C), minimum -25°C.
Altitude: no more than 2000m (coordinate with the manufacturer when it exceeds 2000m).
Air humidity: the average daily relative humidity is not more than 95%, and the monthly average relative humidity is not more than 90%;
Note: Negotiate with our company when ordering with special conditions of use.
The solid insulation performance is fully verified through five core standard tests including dielectric strength test, partial discharge test, aging life test, mechanical strength test and pollution test, ensuring stable and reliable insulation performance under various complex and harsh operating conditions.
Daily maintenance mainly focuses on visual inspection of insulation integrity, avoidance of mechanical damage and strong vibration, real-time monitoring of cabinet temperature and humidity, and regular insulation resistance testing to effectively prevent insulation aging and peeling risks.