Direct Supply Three-phase outdoor vacuum recloser/Reclosure-38kV to 44kV

  • Direct Supply Three-phase outdoor vacuum recloser/Reclosure-38kV to 44kV

Key attributes

Brand ROCKWILL
Model NO. Direct Supply Three-phase outdoor vacuum recloser/Reclosure-38kV to 44kV
Rated voltage 38kV
Rated normal current 630A
Rated short circuit breaking current 16kA
Power frequency withstand voltage 80kV/min
Rated lightning impulse voltage 185kV
manual closing No
Series RCW

Description

Description:

As a pioneering OEM in China’s recloser sector, we leverage decades of R&D strength to set the original industry standards, build a fully autonomous full-chain production system, and provide reliable solutions for power grid projects.

The RCW series Three-phase outdoor vacuum recloser can use on overhead distribution lines as well as distribution substation applications for all voltage classes 11kV up to 38kV at 50/60Hz power system.  and it’s rated current can reach 1250A.The RCW series Three-phase outdoor vacuum recloser integrates the functions of control, protection, measurement, communication, fault detection, on-linemonitoring of closing or opening.The RCW series Three-phase outdoor vacuum recloser is mainly combined with integration terminal, current transformer, permanent magnetic actuator and it’s recloser controller.

Features:

  • Optional grades available in rated current range.
  • With optional relay protection and logic for user selection.
  • With optional communication protocols and I/O ports for users to choose.
  • PC software for controller testing, setup, programming, updates.
  • Solving the dual challenges of tropical heat and humidity
  • Resistant to salt fog corrosion, suitable for offshore / coastal power applications
  • Fully sealed design, preventing sand and dust from affecting
  • Operable in wide temperature range: -30°C to +40°C, handling extreme temperature variations

Parameters:

The voltage classes of some of these Automatic Reclosers include 6kV to 69kV. Rated Short-Circuit Breaking Current includes 8kA to 31.5kA and customization is available.

Rated maximum voltage

38kV

Rated maximum current

1250A

Rated frequency

50Hz

Rated short circuit breaking current

12.5kA

Rated peak value withstand current

31.5kA

Rated 1min power frequency withstand voltage (Three-phase Epoxy resin pole)

85kV

Rated lightning impulse voltage (Three-phase Epoxy resin pole)

185kV

Operation sequence

C-0.3-CO-180-CO (Spring mechanism)

Mechanical life

n:10000 (Spring mechanism)

Power supply and operating voltage     

110/220V (Customized)

Ratio of current transformer

400/1A (Customized)

Number of voltage sensors (Three-phase Epoxy resin pole)

≤6

Opening time

≤50ms (Spring mechanism)

 

With optional relay protection & logics for user choice

Instantaneous over-current protection

Timing over-current protection

Negative sequence over-current protection

Directional over-current protection(⁽¹⁾)

Over-voltage protection / Under voltage protection

Programmable protection relay curves (total 10 nos ANSI/IEC curves)

Cold load pickup protection TCC + Hot line tag

Earth protection E/F SEF + Zone- Sequence Co-ordination

More relay functions can be customized

With optional communication protocols & I/O port for user choice

RS-232 and RS-485 ports supporting

DNP3.0 communication protocol support

Modbus communication protocol is optional

IEC 60870-501 communication protocol support

IEC 60870-5-104 communication protocol support

The recloser can communicate through GPRS(or) GSM(or) GPRS/GSM module with English or Specified language

With optional functions for use

Rated currents, System phase current,

Rated voltages, System phase voltage and secondary low voltage power supply voltage Frequency

power (kWh), reactive power (kVarh), power factor

With optional reclosing interval for user pre-program

reclosing times setting support

Dead time setting support

With events recording function

SOE 10000 operations record

Fault record and normal operation record

Note:mean should customized by manufacturer if needed

Environmental requirement:

Maximum temperature:

+40°C

Minimum temperature:

-30°C

Monthly average humidity

95%

Humidity:

90%

Above sea level:

2500m or higher

Ambient air Not apparently polluted by corrosive and flammable gas, vapor

 

 Product show:

image.png

What are the mechanical failures of Three-phase outdoor vacuum recloser?

Operating Mechanism Faults:

Spring-Operated Mechanism:

  • Spring Fatigue: Spring fatigue is a common issue. If the spring remains compressed for a long time or is frequently operated, it may lose its elasticity, causing the closing speed to slow down or the closing position to be inaccurate. Additionally, mechanical transmission components of the spring-operated mechanism, such as connecting rods and toggle arms, can wear out, deform, or become stuck, affecting the accuracy and reliability of the opening and closing operations.

Permanent Magnet-Operated Mechanism:

  • Magnet Demagnetization: Demagnetization of the permanent magnet is a potential fault in permanent magnet-operated mechanisms. High-temperature environments, strong vibrations, or prolonged exposure to high currents can weaken the magnetic properties of the permanent magnet, affecting the performance of the operating mechanism. Furthermore, faults in the control circuit of the permanent magnet-operated mechanism, such as capacitor aging or electronic component failure, can also lead to abnormal opening and closing operations.

Transmission Component Faults:

  • Loose or Detached Connecting Rods: In outdoor vacuum reclosers, the transmission connecting rods may loosen or even detach over time due to vibration, corrosion, or other factors. This can prevent the opening and closing actions from being transmitted properly, causing the recloser to fail to operate correctly.

  • Wear or Breakage of Pivot Pins: Pivot pins can wear out during rotation. Severe wear can increase the clearance between transmission components, affecting the precision of the opening and closing actions. If a pivot pin breaks, it can directly interrupt the transmission chain of the recloser, preventing it from performing opening and closing operations.

Documentation Resource Library outdoor vacuum Auto Circuit recloser

DEKRA Recloser Test Report
Public.
DEKRA Recloser Test Report
Test Report
English
15kV/27kV/38kV outdoor auto break vacuum recloser brochure
Restricted.
15kV/27kV/38kV outdoor auto break vacuum recloser brochure
Brochure
English
Consulting
Consulting
10 to 38kV auto vacuum break recloser Catalog
Restricted.
10 to 38kV auto vacuum break recloser Catalog
Catalogue
English
Consulting
Consulting
38kV automatic recloser technology specification
Restricted.
38kV automatic recloser technology specification
Technical Data
English
Consulting
Consulting

FAQ for outdoor vacuum Auto Circuit recloser

Q: Does Rockwill offer a cost-effective alternative that is more budget-friendly than the standard RCW+ series?
A:

Yes. The RCWP configuration offers a cost-optimized option within the RCW+ family. It includes dual sensors (voltage + current), flagship controller, and 30,000 mechanical operations with permanent magnet operating mechanism driving three-phase linkage.

To achieve a more affordable price point, the following downgrade options are available:

  • Remove permanent magnet lock box
  • Remove lockout function
  • Downgrade voltage sensor specification
  • Downgrade controller specification (e.g., from flagship to standard)

This allows customers to start with a compliant, reliable base platform and only pay for the features they actually need.

Q: What are the key differences between Rockwill's RCW series recloser and a ZW32-type vacuum circuit breaker?
A:
  • Design Purpose: Purpose-built recloser with auto-reclosing logic — ZW32-type VCB is a basic circuit breaker or demarcation switch
  • Material: Silicone rubber / Epoxy (superior aging & water absorption) — DMC/SMC molded (higher water absorption, faster aging)
  • Protection Logic: Full recloser control with configurable protection curves — limited or no recloser logic
  • Grid Compatibility: Designed with integrated recloser control, sensors, and communication for international distribution automation (IEC 62271-111 / ANSI C37.60) — standalone VCB requiring external controller for automation; primarily designed for basic protection
  • Test Reports: Full type test reports available — varies by manufacturer

Summary: A ZW32-type VCB cannot be directly substituted for a recloser in most international distribution automation applications. The RCW series provides the protection logic, sensor integration, and control intelligence required for modern smart grid deployment.

Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Message
Inquiry
Email
E-mail
WhatsApp
WhatsApp
Chat
Chen/CEO