| Brand | ROCKWILL |
| Model NO. | Live tank SF6 gas circuit breaker-40.5kV to 363kV |
| Rated voltage | 72.5kV |
| Rated frequency | 50/60Hz |
| Series | RHB |
The RHB type Live tank SF6 gas circuit breaker is specifically designed for outdoor high - voltage environments. Utilizing self - blast arc - extinguishing technology and taking advantage of the excellent insulating and arc - extinguishing properties of SF₆ gas, it can quickly quench arcs, ensuring the efficient interruption of fault currents. With a compact and robust structure, it can adapt to various harsh weather conditions. It boasts high reliability and a long service life, which can significantly reduce maintenance frequency, making it a key device for enhancing the safety and stability of power systems.
SF6 gas is used for arc extinguishing
Monitor with a pointer-type density relay
Adopt the self-blast arc extinguishing principle
Adopt pointer-type density relays for pressure and density monitoring
RHB-40.5
| Item | Unit | Parameter |
| Rated voltage | kV | 40.5 |
| Rated frequency | Hz | 50/60 |
| Rated current | A | up to 4000 |
| Rated short-time withstand current, up to 3 s | kA | up to 63 |
| Rated peak withstand current | kA | 80 |
| Rated short-duration power-frequency withstand voltage( 1 min) | kV | 95 |
| Power-frequency withstand voltage( 1 min ),across open contacts | kV | 95 |
| Rated lightning impulse withstand voltage 1.2/50 us | kV | 200 |
| Rated lightning impulse withstand voltage 1.2/50 us, across open contacts | kV | 250 |
| Rated filling pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.5 |
| Minimum functional pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.4 |
| Temperature range (ambient) | ℃ | -30...+40 |
| Type of installation | outdoor | |
| Partial discharge capacity | PC | <5 |
| SF6 leakage rate per year | <0.5% | |
| Maintenance cycle | Year | 30 |
RHB-72.5
| Item | Unit | Parameter |
| Rated voltage | kV | 72.5 |
| Rated frequency | Hz | 50 |
| Rated current | A | up to 4000 |
| Rated short-time withstand current, up to 3 s | kA | up to 63 |
| Rated peak withstand current | kA | 100 |
| Rated short-duration power-frequency withstand voltage( 1 min) | kV | 140 |
| Power-frequency withstand voltage( 1 min ),across open contacts | kV | 160 |
| Rated lightning impulse withstand voltage 1.2/50 us | kV | 325 |
| Rated lightning impulse withstand voltage 1.2/50 us, across open contacts | kV | 375 |
| Rated filling pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.5/0.6 |
| Minimum functional pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.5/0.5 |
| Temperature range (ambient) | ℃ | -30...+40 |
| Type of installation | outdoor | |
| Partial discharge capacity | PC | <5 |
| SF6 leakage rate per year | <0.5% | |
| Maintenance cycle | Year | 30 |
RHB-123/145
| Item | Unit | Parameter | |
| Rated voltage | kV | 123 | 145 |
| Rated frequency | Hz | 50/60 | |
| Rated current | A | up to 4000 | |
| Rated short-time withstand current, up to 3 s | kA | up to 63 | |
| Rated peak withstand current | kA | 100 | |
| Rated short-duration power-frequency withstand voltage( 1 min) | kV | 230 | 275 |
| Power-frequency withstand voltage( 1 min ),across open contacts | kV | 265 | 315 |
| Rated lightning impulse withstand voltage 1.2/50 us | kV | 550 | 650 |
| Rated lightning impulse withstand voltage 1.2/50 us, across open contacts | kV | 650 | 750 |
| Rated filling pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.6 | |
| Minimum functional pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.5 | |
| Temperature range (ambient) | ℃ | -30...+40 | |
| Type of installation | outdoor | ||
| Partial discharge capacity | PC | <5 | |
| SF6 leakage rate per year | <0.5% | ||
| Maintenance cycle | Year | 30 | |
RHB-170
| Item | Unit | Parameter |
| Rated voltage | kV | 170 |
| Rated frequency | Hz | 50/60 |
| Rated current | A | up to 4000 |
| Rated short-time withstand current, up to 3 s | kA | up to 63 |
| Rated peak withstand current | kA | 125 |
| Rated short-duration power-frequency withstand voltage( 1 min) | kV | 275 |
| Power-frequency withstand voltage( 1 min ),across open contacts | kV | 315 |
| Rated lightning impulse withstand voltage 1.2/50 us | kV | 650 |
| Rated lightning impulse withstand voltage 1.2/50 us, across open contacts | kV | 750 |
| Rated filling pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.5 |
| Minimum functional pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.4 |
| Temperature range (ambient) | ℃ | -40...+40 |
| Type of installation | outdoor | |
| Partial discharge capacity | PC | <5 |
| SF6 leakage rate per year | <0.5% | |
| Maintenance cycle | Year | 30 |
RHB-252
| Item | Unit | Parameter |
| Rated voltage | kV | 252 |
| Rated frequency | Hz | 50/60 |
| Rated current | A | up to 4000 |
| Rated short-time withstand current, up to 3 s | kA | up to 63 |
| Rated peak withstand current | kA | 100/125 |
| Rated short-duration power-frequency withstand voltage( 1 min) | kV | 460 |
| Power-frequency withstand voltage( 1 min ),across open contacts | kV | 530 |
| Rated lightning impulse withstand voltage 1.2/50 us | kV | 1050 |
| Rated lightning impulse withstand voltage 1.2/50 us, across open contacts | kV | 1200 |
| Rated filling pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.6/0.6 |
| Minimum functional pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.5/0.5 |
| Temperature range (ambient) | ℃ | -30...+40 |
| Type of installation | outdoor | |
| Partial discharge capacity | PC | <5 |
| SF6 leakage rate per year | <0.5% | |
| Maintenance cycle | Year | 30 |
RHB-363
| Item | Unit | Parameter |
| Rated voltage | kV | 363 |
| Rated frequency | Hz | 50/60 |
| Rated current | A | up to 4000 |
| Rated short-time withstand current, up to 3 s | kA | up to 63 |
| Rated peak withstand current | kA | 100/125 |
| Rated short-duration power-frequency withstand voltage( 1 min) | kV | 450 |
| Power-frequency withstand voltage( 1 min ),across open contacts | kV | 520 |
| Rated lightning impulse withstand voltage 1.2/50 us | kV | 1175 |
| Rated lightning impulse withstand voltage 1.2/50 us, across open contacts | kV | 1175 |
| Rated filling pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.6 |
| Minimum functional pressure (abs. at 20℃) circuit-breaker/other components | Mpa | 0.5 |
| Temperature range (ambient) | ℃ | -30...+40 |
| Type of installation | outdoor | |
| Partial discharge capacity | PC | <5 |
| SF6 leakage rate per year | <0.5% | |
| Maintenance cycle | Year | 30 |
RHB-40.5

RHB-72.5

RHB-123/145

RHB-170

RHB-252

RHB-363