| Brand | ROCKWILL |
| Model NO. | Outdoor Auto Circuit vacuum recloser/reclosure Direct Supply-38kV |
| Rated voltage | 38kV |
| Rated normal current | 630A |
| Rated short circuit breaking current | 16kA |
| Power frequency withstand voltage | 90kV/min |
| Rated lightning impulse voltage | 195kV |
| manual closing | Yes |
| Mechanical lock | No |
| Series | RCW |
Pioneer of China’s recloser track and the first specialized source manufacturer — that’s who we are after decades of focused efforts. We’ve strengthened our foundation via tech breakthroughs, guided the industry through standard-setting, and built a fully independent full-chain system from core R&D to mass production and delivery.
The RCW series automatic circuit reclosers are designed for use on overhead distribution lines and distribution substation applications at a voltage class of 38kV, 50/60Hz power systems, with a rated current up to 1250A. They integrate control, protection, measurement, communication, fault detection, and online monitoring of closing/opening operations. The RCW series vacuum recloser is mainly composed of an integrated terminal, current transformer, permanent magnetic actuator, and its recloser controller.

Full-Vacuum Arc Extinguishing System:Utilizes longitudinal magnetic field vacuum interrupters and epoxy-cast poles, with a short-circuit breaking capacity of 16kA/25 cycles and a mechanical lifespan exceeding 10,000 operations, suitable for frequent switching scenarios.
Integrated Intelligent Control Platform:Equipped with FTU and edge computing modules, supports GOOSE communication, fault waveform recording, and seamless SCADA system integration, enabling remote iterative updates of protection logic via cloud platforms.
Industrial-Grade Environmental Endurance Design:Features an IP67-rated enclosure, operates across a wide temperature range (-45℃ to +70℃), and is validated for both salt spray corrosion (Kesternich 1440h) and seismic resistance (intensity 8).
|
Rated maximum voltage |
38kV |
|
Rated maximum current |
1250A |
|
Rated frequency |
50Hz |
|
Rated short circuit breaking current |
12.5kA |
|
Rated peak value withstand current |
31.5kA |
|
Rated 1min power frequency withstand voltage (Three-phase Epoxy resin pole) |
90kV |
|
Rated lightning impulse voltage (Three-phase Epoxy resin pole) |
195kV |
|
Operation sequence |
C-0.5-CO-2-CO-5-CO (Magnetic actuator) |
|
Mechanical life |
n:30000 (Magnetic actuator) |
|
Power supply and operating voltage |
110/220V (Customized) |
|
Ratio of current transformer |
400/1A (Customized) |
|
Number of voltage sensors (Three-phase Epoxy resin pole) |
≤6 |
|
Opening time |
≤30ms (Magnetic actuator) |
|
Closing time |
≤40ms (Magnetic actuator) |
|
Minimum creepage distance |
31, level4 (mm/kV) |
|
Minimum distance between phases |
360mm |
|
Potential transformer |
110/220V (Customized) |
|
Cable length |
6,8,12m (Customized) |
|
Cable clamp (Three-phase Epoxy resin pole) |
4-hole NEMA |
|
Lightning arrester |
≤6 |
|
Mounting type |
Single / double column |
Note:This Outdoor Auto Circuit vacuum recloser/reclosure is available in multiple configurations for 38kV distribution projects. As a High Voltage Recloser Manufacturer, we support customization of rated current, short-circuit breaking current, CT ratio, operation mode, and operating voltage.
The Pole Mounted Recloser design also supports Outdoor Recloser/Reclosure OEM/ODM China services. Please specify the required parameters when ordering.

The controller panel integrates relay protection, communication protocols, measurement functions, reclosing interval settings, and event recording. As a Smart Recloser China Manufacturer, we support customized protection logic and communication options for different distribution automation projects.
Note:mean should customized by manufacturer if needed
Vacuum Arc Quenching Chamber: The core component that uses a vacuum environment to extinguish arcs. It offers advantages such as strong breaking capacity, fast dielectric recovery, and long contact life, effectively ensuring the reliability of the equipment when interrupting fault currents.
Insulating Pillars: Typically made from high-strength, weather-resistant insulating materials such as epoxy resin, these pillars provide reliable insulation support for the vacuum arc quenching chamber and other components, ensuring the insulation performance of the equipment in harsh outdoor environments.
Operating Mechanism: Common types include spring-operated mechanisms and permanent magnet-operated mechanisms. Spring-operated mechanisms are simple in structure, highly reliable, and easy to maintain. Permanent magnet-operated mechanisms, on the other hand, offer advantages such as fast action, low energy consumption, and long mechanical life, enabling quick and precise opening and closing operations of the recloser.
Current Transformers and Voltage Transformers: Some reclosers are equipped with current transformers and voltage transformers to measure current and voltage signals in the line. These transformers provide data support for protective devices and control devices, enabling the monitoring and protection functions of the power system.


|
Maximum temperature: |
+40°C |
|
Minimum temperature: |
-30°C |
|
Monthly average humidity |
95% |
|
Humidity: |
90% |
|
Above sea level: |
2500m or higher |
|
Ambient air Not apparently polluted by corrosive and flammable gas, vapor |
|
The Rockwill standard smart recloser offers high precision with a wide measuring range (2A–16,000A). Simply ensure your normal current is within this standard range when making a selection.
Yes. In addition to the standard 2A–16,000A range, Rockwill provides custom-configured units for ultra-low current measurement and protection in the 0.1A–2A range.
The controller supports SOE with 10,000 operations record, fault record, and normal operation record. This helps utilities analyze fault events, verify protection operations, and improve maintenance planning. It is suitable for Circuit Recloser applications where event traceability is important.
Yes. The controller supports reclosing times setting and dead time setting, allowing users to pre-program the reclosing interval based on different protection schemes. This flexibility is important for Automatic Recloserprojects that require adaptive reclosure strategies.
Yes. We support customized protection, communication, CT ratio, cable length, and mounting type. we also provide Outdoor Recloser/Reclosure OEM/ODM China services.
Yes. The RCWP, a cost-optimized option in the RCW+ series, features dual sensors, flagship controller, and 30,000 operations with permanent magnet three-phase linkage, while offering downgrade options (lock box removal, lockout removal, sensor/controller downgrade) so customers pay only for what they need.
The ZW32-type VCB is a basic circuit breaker or demarcation switch without built-in auto-reclosing logic, whereas the RCW vacuum recloser is specifically engineered as a full-function recloser with integrated protection, sensors, and communication for smart grid applications.
Unlike the ZW32, which requires an external controller for automation, the RCW series complies with IEC 62271-111 and ANSI C37.60, and is supported by complete type test reports.With silicone rubber or epoxy insulation offering superior aging resistance and low water absorption, the RCW series is the professional choice for international distribution automation projects.