Insulation Medium Performance Gap
o Dried Air/N₂ insulation strength is only 1/3 of SF₆, requiring expansion of contact gap from 60mm to ≥150mm.
o Conventional spring mechanisms lack energy to drive rapid closure of large gaps, easily causing contact ablation due to pre-strike.
o Synthetic gases (e.g., C4+CO₂) decompose under arcing, leading to irreversible insulation degradation.
Mechanical Structural Limitations
o National Grid standardization fixes cabinet width at 420mm, restricting longitudinal space.
o Large gaps necessitate longer moving blades in three-position disconnectors, increasing insulation design difficulty.
|
Technical Direction |
Implementation |
Effect |
|
Composite Insulation |
Moving blade + high-strength insulation cover + PTFE partition |
Blocks discharge path; withstands lightning impulse voltage (≥125kV) |
|
Medium Synergy Optimization |
Dried Air/N₂ fill + vacuum interrupter core |
Vacuum interrupter ensures breaking; gas insulation maintains isolation |
|
Zero-Gauge Reliability |
Cabinet passes power frequency/lightning impulse tests (ambient pressure) |
No leakage risk; maintenance safety equals sealed cabinets |
Key Breakthrough: Achieves SF₆-grade insulation at 150mm gap, overcoming medium limitations.
|
Parameter |
SF₆ Ring Main Unit |
Air/Eco-friendly Gas Solution |
|
Contact Gap |
60mm |
≥150mm (incl. insulation cover) |
|
Closing Speed |
Adequate for springs |
Optimized shaft + lightweight blade |
|
Breaking Medium |
SF₆ gas |
Vacuum interrupter + dried air |
|
Zero-Gauge Withstand |
Fails |
Passes 42kV power freq./75kV LI |
|
Environmental Impact |
GWP=23,900 |
GWP=0 (dried air) |
Insulation Verification Process
o Phase 1: 3D electric field simulation (gap field strength <3kV/mm)
o Phase 2: Full/cutoff lightning impulse tests (±200kV)
o Phase 3: Repeated insulation tests post E2-class short-circuit making
Mechanism Reliability Strategy
o Hexagonal nylon shaft: Deformation-resistant lifespan >10,000 ops
o Three-position mechanical interlock: Mandatory anti-misoperation locking
o Making characteristic monitoring: Displacement sensors provide real-time closing speed curves