| Brand | ROCKWILL |
| Model NO. | Eco-Friendly Gas Insulated Switchgear RMU for Urban Distribution Network-12kV |
| Rated voltage | 12kV |
| Rated frequency | 50/60Hz |
| Series | REC |
The ROCKWILL Indoor N2 Insulated Ring Main Unit is a high-performance medium-voltage power distribution device engineered for modern smart grids at 12 kV class. Utilizing 100% nitrogen (N2) insulation (GWP = 0) as a zero-carbon alternative to traditional SF₆ switchgear, this ring main unit delivers reliable power distribution while eliminating greenhouse gas emissions entirely.
The hermetically sealed gas chamber and fully sealed operating mechanism enable maintenance-free long-term operation, significantly reducing lifecycle costs. With IP67 protection for the high-voltage compartment, it solves flashover faults caused by water accumulation in basements and coastal humidity.
Featuring modular busbar connectors that require zero on-site gas work, it enables rapid installation and seamless capacity expansion. Ideal for urban distribution networks, industrial parks, commercial complexes, and legacy SF₆ switchgear green upgrades targeting global low-carbon goals.
Dual Advantages of Environmental Protection & Maintenance-Free:Adopts low-GWP environmental protection gas (compliant with eco-friendly standards) to avoid environmental pollution; the hermetic gas chamber and wear-resistant components realize long-term maintenance-free operation, reducing operation and maintenance costs.
High Operational Safety & Stability:Equipped with advanced gas insulation technology, it has strong resistance to humidity, dust, and corrosion; the built-in overvoltage and short-circuit protection functions ensure stable power supply even in harsh working environments.
Compact Design for Flexible Installation:The compact structure saves installation space, making it suitable for narrow areas such as urban underground power stations and industrial workshops; it supports modular combination to meet diverse distribution network layout needs.
Smart Monitoring for Predictive Management:Optional intelligent online monitoring system tracks gas pressure, temperature, and operating status in real time; it sends early warnings for abnormal conditions, helping users achieve predictive maintenance and improve grid management efficiency.
|
General |
Unit |
Parameter |
|
Rated Voltage |
kV |
12 |
|
Rated Frequency |
Hz |
50 |
|
Power Frequency Withstand Voltage |
V/min |
42/28 |
|
Lightning Impulse Voltage |
kV |
75/85 |
|
Arc Duration |
s |
1 |
|
Primary Component Protection Level (excluding metering cabinet) |
IP67 |
|
|
Cabinet Protection Level |
IP4X |
|
|
Isolation Room Protection Level |
IP2X |
|
|
Operating Power Supply Voltage |
V |
DC: 24 48 110 220 |
|
AC: 110 220 |
||
| Parameter | Unit | IEC Standard Requirement |
|---|---|---|
| Ambient Temperature (Maximum) | °C | +40 |
| Ambient Temperature (Maximum 24-hour average) | °C | +35 |
| Ambient Temperature (Minimum) | °C | -5, -15, or -25 (preferred values, site-dependent) |
| Relative Humidity (24-hour average) | % | ≤ 95 |
| Relative Humidity (Monthly average) | % | ≤ 90 |
| Water Vapour Pressure (24-hour average) | kPa | ≤ 2.2 |
| Water Vapour Pressure (Monthly average) | kPa | ≤ 1.8 |
| Altitude (above sea level) | m | ≤ 1000 |
| Air Purity | — | Not significantly polluted by dust, smoke, corrosive/flammable gases, vapors, or salt |
| Vibration | — | Negligible (from external mechanical sources) |