| Brand | ROCKWILL |
| Model NO. | High-Voltage Vacuum Switch for Mining Mobile Substations |
| Rated frequency | 50/60Hz |
| Series | KJGZY |
The KJGZY flameproof, intrinsically safe permanent-magnet HV vacuum switch feeds mining equipment from mobile substations. Independent breaker, isolating and wiring chambers allow safe live maintenance within a three-chamber flameproof design. A PLC/HMI control core provides 1A-step current setting, fault memory and password locking. Protection covers overload, short circuit, leakage, gas interlocking and emergency shutdown of the upstream supply.
Independent Chambers:Equipped with independent circuit breaker chamber, isolating switch chamber, and wiring chamber, enabling live maintenance, safe and reliable operation and upkeep.
High Precision:1A step setting for higher precision.
Effective Explosion Protection:Integrated three-chamber design ensures reliable explosion protection.
Digital Control:Adopts an industrial programmable logic controller (PLC) and human-machine interface (GOT) to form the core control system, featuring stable performance, precise protection, and simple maintenance. It also has fault memory and password locking functions.
Stable Operation:Adopts an industrial programmable logic controller (PLC) and human-machine interface (GOT) to form the core control system, featuring stable performance, precise protection, and simple maintenance.
Safety and Reliability:Current can be continuously set with a step value of 1A, enabling safe and reliable live maintenance, operation and upkeep. All faults trigger the high-voltage side vacuum circuit breaker to trip via signal lines, reducing breaking current.
Multiple Protections:Equipped with protection functions including overload, short circuit, overvoltage, undervoltage, leakage, leakage locking, phase loss, over-temperature, wind power and gas locking, emergency shutdown of upper-level power supply, etc. It can also protect against faults fed back from the low-voltage side of the mobile substation.
Modular Design:Comes with standard RS232/485 communication interfaces, featuring powerful remote communication and control functions. It has a small size, reasonable structure and intuitive operation.
| Parameter | Value |
|---|---|
| Rated voltage | 12 kV |
| Rated current | 1250 A |
| Rated frequency | 50 Hz |
| Rated short-circuit breaking current | 12.5 kA |
| Rated short-circuit making current (peak) | 31.5 kA |
| Rated peak withstand current | 31.5 kA |
| Rated short-time withstand current | 12.5 kA / 2 s |
| Power-frequency withstand voltage (1 min) | 28 kV |
| Lightning impulse withstand voltage | 75 kV |
| Mechanical life (circuit breaker) | 10,000 operations |
| Rated short-circuit breaking operations | 30 operations |
| Explosion protection type | Ex d [ib] I Mb |
| Degree of protection | IP54 |
| Communication interface | RS232 / RS485 |