| Brand | ROCKWILL |
| Series | RPS |
| Rated voltage | 38kV |
| Short Circuit Current | 16/20/25kA |
| Rated normal current | 1250A |
| Earth fault breaking current | 130A |
| Peak withstand current | 50kA |
The RPS-38 is a 38kV-class SF6-insulated pole-mounted load break switch (switch-disconnector) designed for distribution automation systems. KEMA type-tested with a 3mm stainless steel sealed tank, it delivers maintenance-free operation across extreme environments (-45°C to +85°C). Available in manual, motorized, remote-controlled, and automatic sectionalizer configurations.

| Parameter | Value/Description |
|---|---|
| Rated Voltage | 38kV |
| Rated Current | To be specified |
| BIL (Basic Insulation Level) | 170/200/215kV |
| Power Frequency Withstand Voltage | 70/80/95kV |
| Short Circuit Current | 16/20/25kA |
| Tank Material | 3mm stainless steel |
| Bushing Options | Porcelain/silicone rubber/cable termination |
| Welding Design | Minimal weld lines for corrosion resistance |
| Operation Mechanism | Patented spiral spring |
| Operation Speed | IEC62271-100 compliant |
| Operation Types | Manual/motorized/remote/automatic sectionalizer |
| Temperature Range | -45℃ to +85℃ |
| Humidity Tolerance | 95% monthly average |
| Maximum Altitude | 2500m+ (custom higher available) |
| Pollution Resistance | Salt/industrial atmospheres |



| Parameter | Value |
|---|---|
| Ambient Temperature | -45°C ~ +85°C |
| Humidity | ≤95% monthly average |
| Altitude | ≤2500m (higher options available) |
| Pollution Resistance | Salt, corrosive industrial atmospheres |
It is a 38kV-class SF6-insulated pole-mounted load break switch (switch-disconnector) for distribution automation; it switches load current but does not break short-circuit current.
Yes, we are a China Manufacturer. OEM/ODM covers rated parameters, bushing type, controller/communication protocol, branding and packaging.
Manual, motorized, remote-controlled and automatic sectionalizer versions; bushings in porcelain, silicone rubber or cable termination.
The SF6 load break switch features an arc-resistant design with manual override capability for safe emergency operation upon control system failure.