| Brand | ROCKWILL |
| Series | RMR |
| Rated Voltage | 12 kV |
| Rated Short-Circuit Breaking Current | 20 kA / 25 kA |
| Lightning Impulse Withstand Voltage | 75 kV |
| Rated Frequency | 50 Hz / 60 Hz |
This SF6 gas insulated ring main unit, fully complying with IEC 62271-200 and IEC 62271-103 international standards.
All live conductive components are encapsulated in airtight 304 stainless steel gas tank, with SF6 acting as insulation and arc-extinguishing medium. The equipment adopts independent three-compartment layout (busbar compartment, gas switch compartment, cable compartment), equipped with integrated three-position load switch and earthing switch. Standard C/F/V functional modules can be freely combined to form ring, radial and sectionalized medium voltage distribution networks.
The compact vertical split cabinet structure matches the physical picture, suitable for indoor box substations, urban narrow distribution stations and commercial power distribution projects, realizing reliable switching, fault isolation and overcurrent protection for 12kV grids.
Reliable SF6 Hermetic Insulation:Fully welded stainless steel gas tank with annual SF6 leakage rate ≤0.03%, equipped with gas density monitor for real-time internal pressure monitoring, avoiding insulation breakdown caused by gas loss.
Modular Three-Compartment Safety Layout:Independent partition design for busbar, switching and cable chambers, with optional IAC internal arc resistance structure to meet IEC anti-arc safety requirements.
Complete 5-Way Mechanical & Electrical Interlock:Standard five-prevention interlock mechanism prevents misoperation of switch, earthing device and cabinet door, fully conforming to IEC safety operation specifications.
Maintenance-Free Long Service Life:Sealed gas chamber isolates dust, moisture and corrosive gas; 20-year design life without regular gas refilling, mechanical operation life up to 5,000 cycles.
Wide Global Grid Compatibility:Supports 50Hz & 60Hz dual frequency, compatible with overhead cable incoming/outgoing, transformer protection and distributed new energy power supply systems.
Intelligent Expansion Reserved:Reserved installation space for DTU remote monitoring unit, CT/PT measuring components for feeder automation upgrade.
| Rated Voltage | 12 kV |
| Rated Frequency | 50 Hz / 60 Hz |
| Rated Continuous Current | 630 A |
| Rated Short-Time Withstand Current (3 s) | 20 kA / 25 kA |
| Rated Short-Circuit Breaking Current | 20 kA / 25 kA |
| Insulation Medium | SF6 Gas |
| Main Switch Type | Three-position SF6 Load Break Switch |
| Power Frequency Withstand Voltage | 42 kV |
| Lightning Impulse Withstand Voltage | 75 kV |
| SF6 Annual Leakage Rate | ≤0.03 % |
| Internal Arc Classification (IAC) | IAC A FLR 20 kA (optional) |
| Mechanical Operation Life | ≥5,000 cycles |
| Rated Contact & Winding Temperature Rise | 55 K |
| Insulation Class | Class A |
| Protection Degree | IP67 (Hermetic SF6 Gas Tank), IP4X (Outer Cabinet) |
| Ambient Operating Temperature | -25 ℃ ~ +40 ℃ |
| Max Installation Altitude | ≤2000 m |
| Relative Humidity | Daily average ≤95%, Monthly average ≤90% |
| Design Service Life | 20 years |
| Compliance Standards | IEC 62271-200, IEC 62271-103 |
Urban residential ring distribution networks
Industrial parks, mining and manufacturing power supply
Shopping malls, high-rise buildings and commercial complexes
Photovoltaic & wind power new energy collection stations
Indoor compact kiosk substations and box transformers
Municipal public infrastructure medium voltage power distribution