| Brand | ROCKWILL |
| Series | RMR |
| Rated Voltage | 11kV / 12kV |
| Rated Normal Current | 125A / 630A / 1250A |
| Rated Short-time Withstand Current (3s) | 20kA / 25kA |
| Rated Frequency | 50/60Hz |
IEC-standard compact metal-enclosed SF6 ring main unit, compliant with IEC 62271-200 and IEC 62271-103, suitable for 11kV/12kV medium voltage distribution systems. Adopting fully sealed SF6 gas insulation and integrated load switch structure, it features reliable mechanical interlock, flexible modular combination and long-term maintenance-free operation, widely applied in automated urban and industrial power distribution networks.
IEC Standard Insulation Performance:Fully compliant with international IEC standards. Sealed SF6 gas provides superior dielectric strength and stable arc extinction, effectively preventing high-voltage flashover, short-circuit and leakage faults to ensure safe and stable grid operation.
Compact Modular Design:Miniaturized footprint with expandable modular structure, perfectly suitable for space-limited substations, commercial buildings and industrial parks, greatly improving space utilization.
Dual Safety Protection:Complete mechanical and electrical interlock devices prevent misoperation; real-time SF6 gas pressure monitoring and low-pressure alarm function ensure safe operation and maintenance.
Ultra-long Service Life & Low O&M Cost:Hermetically sealed gas chamber isolates dust, moisture and corrosive substances. Support 20+ years maintenance-free operation, effectively reducing whole life cycle cost.
Strong Grid Adaptability:Supports both ring network and radial network power supply modes, adaptable for industrial, commercial, residential and public facility power distribution projects.
| Item | Specification |
|---|---|
| Standard Compliance | IEC 62271-200, IEC 62271-103 |
| Rated Voltage | 11kV / 12kV |
| Rated Frequency | 50/60Hz |
| Rated Normal Current | 125A / 630A / 1250A |
| Rated Short-time Withstand Current (3s) | 20kA / 25kA |
| Rated Peak Withstand Current | 50kA (for 20kA) / 63kA (for 25kA) |
| 1min Power Frequency Withstand Voltage | 42kV (Phase-to-earth), 48kV (Open contact) |
| Lightning Impulse Withstand Voltage | 75kV (Phase-to-earth), 85kV (Open contact) |
| SF6 Rated Filling Pressure | 0.045 MPa (gauge) |
| SF6 Low Alarm Pressure | 0.025 MPa (gauge) |
| Operating Temperature | -35℃ ~ +40℃ |
| Max. Installation Altitude | ≤2500m |
| Relative Humidity | ≤95% (monthly average, no condensation) |
Mainly used for secondary distribution in urban power grids, industrial zones, residential, medical, educational and commercial facilities as core medium voltage switching equipment.