| Brand | ROCKWILL |
| Series | DKSC |
| Rated voltage | 35 kV |
| Connection group | Z (zigzag) / ZNyn11 |
| Rated capacity range | 100 – 5,500 kVA |
| Rated frequency | 50 / 60 Hz |
Minor adjustments such as modification of auxiliary winding voltage, sensor configuration or enclosure accessories are usually feasible before casting starts.
Once the epoxy winding casting and curing process is completed, core electrical parameters including zero-sequence impedance and vector group cannot be changed.
If the grid grounding scheme, required fault current or short-time withstand duration changes after casting, a redesign and remanufacture will be required.
Any design change request should be submitted as early as possible, and we will issue an updated technical datasheet, cost and delivery revision for approval.
Remote commissioning guidance is included as standard. On-site engineer attendance is an optional service that can be added under the contract.
When engineers attend site, they will check mechanical installation, earthing connection, cable termination quality, sensor wiring, and coordinate with the protection team to verify zero-sequence loop logic.
They will also cross-check measured zero-sequence impedance against factory values, guide energization steps and record initial running data.
The on-site service does not cover civil construction, cable laying or protection relay programming unless these extra items are clearly listed in the service scope.
Third-party witness testing is available upon request. We can coordinate the factory test schedule to accommodate inspectors from the buyer, engineering consultant, certification body or power utility.
Witnessed tests typically include winding resistance, vector group verification, insulation resistance, zero-sequence impedance measurement, power frequency withstand and partial discharge tests. All test procedures follow IEC standards, and the full test data will be signed off by both sides.
If the client requires additional special tests beyond the standard routine scope, we can assess feasibility, timeline and extra cost separately in advance.
Yes. Rockwill earthing transformers are available in both oil-immersed and cast-resin dry-type versions. Oil-immersed units suit outdoor high-capacity applications. Dry cast resin models are preferred for indoor sites with strict fire safety requirements (substations, data centers). Auxiliary secondary winding, PT/CT monitoring assemblies can be equipped for both types.
Vacuum-cast epoxy thin insulation (1–3mm) resists thermal-cycling cracks, is moisture resistant and flame retardant, and is maintenance-free. Both HV and LV windings use copper foil for partial discharge <10 pC, excellent lightning impulse withstand, and high short-circuit resistance.