| Brand | ROCKWILL |
| Model NO. | Oil-Immersed Power Transformer for Regional Transmission-138kV |
| Rated frequency | 50/60Hz |
| Series | S (F) |
As a core transmission equipment, the S (F) series three-phase oil-immersed power transformer is designed for regional transmission networks, stepping down high voltage to medium-voltage levels for substations, industrial parks, and urban systems.
Featuring premium low-loss silicon steel cores and optimized copper windings, it delivers stable power flow over medium distances while minimizing losses. Equipped with reliable tap changers and protection sensors, it ensures fault-safe operation. The robust sealed-tank design withstands harsh environments, guaranteeing long-term operational safety and grid stability.
SF Series 138kV Three-Phase Double-Winding On-Load Tap-Changing Power Transformer
| Model | Rated Capacity (MVA) | High Voltage (kV) | HV Tapping Range | Low Voltage (kV) | Connection Group | Short-circuit Impedance (%) | No-load Loss (kW) | Load Loss (kW) | No-load Current (%) |
|---|---|---|---|---|---|---|---|---|---|
| SF-20000/138 | 20 | 138 | ±8×1.25% | 11, 20, 35 | YNd11 | 9.0 | 18.0 | 95.0 | 0.60 |
| SF-31500/138 | 31.5 | 138 | ±8×1.25% | 11, 20, 35 | YNd11 | 10.0 | 25.0 | 135.0 | 0.55 |
| SF-40000/138 | 40 | 138 | ±8×1.25% | 11, 20, 35 | YNd11 | 10.0 | 30.0 | 160.0 | 0.50 |
| SF-50000/138 | 50 | 138 | ±8×1.25% | 11, 20, 35 | YNd11 | 10.5 | 35.0 | 190.0 | 0.45 |
| SF-63000/138 | 63 | 138 | ±8×1.25% | 11, 20, 35 | YNd11 | 10.5 | 42.0 | 230.0 | 0.40 |
| SF-80000/138 | 80 | 138 | ±8×1.25% | 11, 20, 35 | YNd11 | 12.0 | 50.0 | 280.0 | 0.35 |
| SF-100000/138 | 100 | 138 | ±8×1.25% | 11, 20, 35 | YNd11 | 12.0 | 60.0 | 340.0 | 0.30 |
| SF-160000/138 | 160 | 138 | ±8×1.25% | 11, 20, 35 | YNd11 | 14.0 | 85.0 | 520.0 | 0.25 |

Power transformers are classified by insulation and cooling method, voltage function, and core structure. By insulation and cooling, they fall into liquid-insulated (oil-immersed) and dry-type — oil-immersed transformers dominate transmission applications up to 345 kV and above with standardized cooling like ONAN, ONAF and OFAF, while dry-type transformers are primarily used indoors at lower voltages up to 35 kV.
By voltage function, they are divided into step-up transformers (used in power plants to raise generator voltage to transmission levels), step-down transformers (used in substations to reduce transmission voltage for sub-transmission or distribution), and autotransformers (employed for fixed-ratio system interconnections, offering high efficiency in transmission grids). By core structure, they include core-type transformers (with windings surrounding core limbs, common in EHV applications) and shell-type transformers (with core surrounding the windings).