占位边距

SF6-Free Single Circuit Air-Insulated Ring Main Unit-12kV

  • SF6-Free Single Circuit Air-Insulated Ring Main Unit-12kV
  • SF6-Free Single Circuit Air-Insulated Ring Main Unit-12kV

Key attributes

Brand ROCKWILL
Model NO. SF6-Free Single Circuit Air-Insulated Ring Main Unit-12kV
Rated voltage 12kV
Rated normal current 630A
Rated frequency 50/60Hz
Series XGN

Description

Sealed air-insulated ring main unit for single-circuit distribution with SF₆-free technology. Air at atmospheric pressure in a sealed enclosure delivers reliable insulation with no gas monitoring or leakage risk. Integrated load break and earthing switches provide safe switching and visible isolation for urban substations, industrial parks, and commercial facilities.

Product advantages

  • Normal pressure sealing: No leakage risk, ensuring excellent insulation performance.
  • Air insulation: The gas requires no treatment. Through improved processing techniques, selection of high-grade materials, and optimized electric field design, it meets the demand for miniaturization.
  • Simple operating mechanism: With a simple and stable structure, its mechanical service life can reach 10,000 times.
  • Miniaturization: Its volume is 1/5 that of KYN, equivalent to the volume of conventional pressure-type ones, saving space.
  • Standardized expansion method: Facilitates on-site installation and reduces power outage time.

Parameters

Name

Unit

Parameter Value

Rated Voltage (Ur)

kV

12

Rated Frequency (fr)

Hz

50

Rated Current (Ir)

A

630

Short - time Power Frequency Withstand Voltage (Ud)

Between Fractures

kV

48

Between Phases

kV

42

Phase to Ground

kV

42

Lightning Impulse Withstand Voltage (Up)

Between Fractures

kV

95

Between Phases

kV

75

Phase to Ground

kV

75

Rated Short - time Withstand Current (Ik)

kA

20/25

Rated Short - circuit Duration (tk)

s

4

Rated Peak Withstand Current (Ip)

kA

50/63

Rated Short - circuit Breaking Current (Isc)

kA

20/25

Rated Short - circuit Making Current (Ima)

 

Vacuum Interrupter

kA

50/63

Earthing Switch

   

Auxiliary Circuit and Control Circuit

Rated Voltage (Ua) DC/AC

V

<400

Power Frequency Withstand Voltage (1min)

V

2000

Mechanical Life

 

Circuit Breaker

Times

10000

Disconnecting Switch

Times

3000

Earthing Switch

Times

3000

Electrical Life  

Circuit Breaker

Class

E2

Earthing Switch

Class

E2

Protection Grade of Cabinet Enclosure

 

IP4X

Protection Grade of Sealed Box

 

IP65

Environmental Conditions

Ambient Temperature (Max / 24h Avg / Min) +40 °C / ≤+35 °C / -25 °C
Altitude ≤ 1000 m
Relative Humidity (Max at 25°C / Max at 40°C) 95% / 50%
Water Vapor Pressure (Max / Min) 2.2 kPa / 0.1 kPa
Solar Radiation ≤ 1000 W/m²
Pollution Class Class II

Solutions for Ring Main Unit

  • Optimization Design Scheme for the 12kV Air-Insulated Ring Main Unit Isolating Gap to Reduce Breakdown Discharge Probability
    With the rapid development of the power industry, the ecological concept of low-carbon, energy-saving, and environmental protection has been deeply integrated into the design and manufacturing of power supply and distribution electrical products. The Ring Main Unit (RMU) is a key electrical device in distribution networks. Safety, environmental protection, operational reliability, energy efficiency, and economy are inevitable trends in its development. Traditional RMUs are primarily represented
  • Design Solution of 24kV Dry Air Insulated Ring Main Unit
    The combination of Solid Insulation Assist + Dry Air Insulation represents the development direction for 24kV RMUs. By balancing insulation requirements with compactness and employing solid auxiliary insulation, insulation tests can be passed without significantly increasing phase-to-phase and phase-to-ground dimensions. Encapsulating the pole column solidifies the insulation for the vacuum interrupter and its connecting conductors.Maintaining the 24kV outgoing busbar phase spacing at 110mm, the

FAQ for Ring Main Unit

Can environmentally friendly cabinets be used in alpine regions with low temperatures?
Yes, they are highly suitable for alpine regions. The insulating gas (dry air, N2) used in eco-friendly cabinets has a very low boiling point (N2 boiling point: -195.8℃) and will not liquefy even at ultra-low temperatures (-40℃ or lower). The cabinet's structural materials and seals are also selected for low-temperature resistance to avoid performance degradation due to cold brittleness. They are widely used in alpine regions such as northern China and high-altitude areas.
Are environmentally friendly cabinets suitable for humid coastal areas?
Yes, but they need to adopt anti-corrosion and moisture-proof designs. Humid coastal areas have high air humidity and salt spray corrosion, so environmentally friendly cabinets for these areas use anti-corrosion materials (e.g., hot-dip galvanized steel, stainless steel), enhanced sealing structures, and dry air with a dew point of ≤ -50℃. Some high-protection models (IP65) can effectively resist salt spray and moisture erosion, ensuring stable operation.
Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Message
Inquiry
WhatsApp
WhatsApp
Chat
Chen/CEO