| Brand | ROCKWILL |
| Model NO. | SF6 Gas Insulated Metal-clad switchgear for MV Substation Distribution- 25.8 to 40.5kV |
| Rated voltage | 27.5kV |
| Rated frequency | 50/60Hz |
| Maximum operating voltage | 27.5kV |
| Series | RGIS |
The RGIS series of SF6 gas - insulated metal - clad switchgear is specifically designed for three - phase three - wire 50/60 Hz systems with a maximum voltage of 40.5 kV. With a rated voltage reaching up to 40.5 kV, it features either horizontally or vertically installed vacuum circuit breakers. The switchgear encompasses a comprehensive set of components like vacuum circuit breakers, meters, and relays.
Excellent Insulation Performance
Reliable Arc - Extinguishing Performance
Fully Enclosed Structure
Modular Design
Good Explosion - Proof Performance
Perfect Anti - Misoperation Function
Low Maintenance Workload
| Designation of type | Unit | RGIS - G10 | RGIS - G20 | RGIS - G80 | RGIS - G90 |
|---|---|---|---|---|---|
| Rated voltage | kV | 25.8 | 40.5 | 40.5 | 27.5 |
| Rated power frequency withstand voltage | kV | 50 | 95 | 95 | 95 |
| Rated lightning impulse withstand voltage | kV | 125 | 185 | 185 | 185 |
| All voltage values apply for an insulating gas pressure, absolute, 20℃ | kPa | 110 | 110 | 110 | 110 |
| Rated frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 |
| Rated busbar current | A | up to 2000 | up to 1250 | up to 1250 | up to 1250 |
| Rated feeder current | A | 630/ 1250/ 2000 | 630/ 1250 | 630/ 1250/ 2000 | 630/ 1250/ 2000 |
| Rated peak withstand current | kA | 63 | 80 | 80 | 80 |
| Rated short time current 4 seconds | kA | 25 | 31.5 | 31.5 | 31.5 |
| Rated short circuit breaking current of circuit breaker | kA | 25 | 31.5 | 31.5 | 31.5 |
| Rated short circuit making current of circuit breaker | kA | 63 | 80 | 80 | 80 |
| Rated operating sequence | - | O - 0.3s - CO - 3min - CO | |||
| Closing time | ms | 75 | 60±5 | 60±5 | 60±5 |
| Opening time | ms | 60 | 40±5 | 40±5 | 40±5 |
| Insulating gas | - | SF₆ | |||
| Rated filling pressure, absolute, 20℃ | kPa | 130 | |||
| Minimum operating pressure, absolute, 20 ℃kPa | kPa | 120 | |||
| Rated data: Auxiliary voltage | V | 220DC /110-125V DC | |||


| Environmental Parameter | Standard Value |
|---|---|
| Ambient air temperature — upper limit | +40 °C |
| Ambient air temperature — 24 h average | +35 °C |
| Ambient air temperature — lower limit | –25 °C |
| Altitude above sea level | ≤ 1 000 m |
| Relative humidity — 24 h average | ≤ 95% (at +40 °C) |
| Relative humidity — monthly average | ≤ 90% |
| Water vapour pressure — 24 h average | ≤ 2.2 kPa |
| Water vapour pressure — monthly average | ≤ 1.8 kPa |
| Solar radiation | ≤ 1 000 W/m² |
| Wind speed (outdoor) | ≤ 34 m/s (mild) |
| Pollution degree (indoor) | Class II |
| SF₆ gas decomposition products | ≤ 1 μL/L (SO₂F₂) |
Yes. The switchgear encompasses comprehensive components including meters, relays, and control units, supporting intelligent grid control and automation. Compatible with SCADA and remote monitoring systems.
The fully enclosed SF₆ insulated structure isolates all live parts from external environmental impacts, ensuring low maintenance workload throughout the service life. SF₆ gas insulation eliminates dust, moisture, and corrosion concerns.
The RGIS features vacuum circuit breakers (horizontally or vertically installed) with an operating sequence of O-0.3s-CO-3min-CO. Closing time is 60±5 ms and opening time is 40±5 ms — providing rapid and reliable switching.