占位边距

Single-phase Vacuum Recloser (Reclosure) Wholesaler-15.6kV

  •  Single-phase Vacuum Recloser (Reclosure) Wholesaler-15.6kV

Key attributes

Brand ROCKWILL
Model NO. Single-phase Vacuum Recloser (Reclosure) Wholesaler-15.6kV
Rated voltage 15.6kV
Rated normal current 400A
Rated short circuit breaking current 12.5kA
Power frequency withstand voltage 60kV/min
Rated lightning impulse voltage 125kV
manual closing No
Series RCW

Description

As a pioneering original equipment manufacturer (OEM) in China’s recloser/reclosure industry, we have accumulated decades of R&D expertise, taken the lead in establishing the original industry standards, built a fully independent end-to-end production system, and delivered reliable product solutions for power grid construction.

The 15.6kV Single-phase outdoor Automatic Smart recloser/reclosure is an intelligent outdoor switching device specifically designed for medium-voltage distribution networks. Using vacuum as the arc-extinguishing medium, this equipment can quickly interrupt fault currents and effectively isolate short-circuits, overloads, and other faults in the distribution grid.

It features an automatic reclosing function that restores power supply automatically after fault elimination, significantly reducing power outage time and improving power supply reliability. With its compact and rugged outdoor structure design, it adapts to various harsh natural environments—stable operation in high temperatures, severe cold, high humidity, or sandy conditions—making it a vital device for ensuring safe and efficient operation of medium-voltage power lines.

 Rows of outdoor vacuum reclosers ready for shipment at a professional Vacuum Recloser supplier factory.

Key Features

High-efficiency Arc Extinguishing Performance

  • Adopting vacuum arc extinguishing technology, it features strong insulation and rapid arc extinction. It prevents arc reignition, extends the equipment's service life, and reduces maintenance costs.

Precise Automatic Reclosing

  • Automatically closes the circuit according to the preset program. It can distinguish between transient and permanent faults. For transient faults, it restores power supply rapidly; for permanent faults, it locks immediately to minimize the power outage scope.

Excellent Environmental Adaptability

  • With a high-strength and corrosion-resistant outer shell and internal protective treatment, it can operate stably in harsh environments, adapting to temperatures ranging from -40°C to +70°C.

Intelligent Monitoring and Remote Control

  • It can monitor key parameters such as current and voltage in real-time and upload data. Supporting remote opening and closing operations, it improves fault handling efficiency and the intelligent level of grid operation and maintenance.

High Safety and Reliability

  • Equipped with complete mechanical and electrical interlocking devices to prevent misoperation, it has a long-life design with tens of thousands of mechanical operation cycles, ensuring stable power supply.

Controller Instruction

This recloser controller offers a variety of optional relay protection logics including over‑current, negative‑sequence, directional, over‑/under‑voltage and earth‑fault protection, with support for ANSI/IEC curves and customizable functions.

Equipped with RS‑232/RS‑485 interfaces and multiple power communication protocols, it supports GPRS/GSM communication, allows pre‑programming of reclosure parameters, and provides electrical parameter measurement together with up to 10 000 SOE event and fault records.

Single-phase outdoor Automatic Smart recloser/reclosure Controller Instruction

Time‑Overcurrent Curves

The following information describes the curve timing for the curve and time dial settings made for the time‑overcurrent elements. The time‑overcurrent relay curves in conform to IEEE C37.112‑1996 IEEE Standard Inverse‑Time Characteristic Equations for Overcurrent Relays.

Single-phase outdoor Automatic Smart recloser/reclosure

Parameters

Rated maximum voltage

15.6kV

Rated maximum current

1250A

Rated frequency

50Hz

Rated short circuit breaking current

12.5kA

Rated peak value withstand current

31.5kA

Rated 1min power frequency withstand voltage(Single-phase Silicone rubber pole (unable the gas))

60kV

Rated lightning impulse voltage(Single-phase Silicone rubber pole (unable the gas))

125kV

Operation sequence

C-0.5-CO-2-CO-5-CO(Magnetic actuator)

Mechanical life

n:30000(Magnetic actuator)

Power supply and operating voltage

110/220V (Customized)

Ratio of current transformer

400/1A (Customized)

Number of voltage sensors(Single-phase Silicone rubber pole (unable the gas))

≤1

Opening time

≤20ms(Magnetic actuator)

Closing time

≤30ms(Magnetic actuator)

Minimum creepage distance

31, level4(mm/kV)

Minimum distance between phases

360mm

Potential transformer

110/220V (Customized)

Cable length

6,8,12m (Customized)

Cable clamp(Single-phase Silicone rubber pole (unable the gas))

2-hole NEMA

Lightning arrester

≤6

Mounting type

Single / double column

With optional relay protection & logics for user choice

Instantaneous over-current protection

Timing over-current protection

Negative sequence over-current protection

Directional over-current protection(⁽¹⁾)

Over-voltage protection / Under voltage protection

Programmable protection relay curves (total 10 nos ANSI/IEC curves)

Cold load pickup protection TCC + Hot line tag

Earth protection E/F SEF + Zone- Sequence Co-ordination

More relay functions can be customized

With optional communication protocols & I/O port for user choice

RS-232 and RS-485 ports supporting

DNP3.0 communication protocol support

Modbus communication protocol is optional

IEC 60870-501 communication protocol support

IEC 60870-5-104 communication protocol support

The recloser can communicate through GPRS(or) GSM(or) GPRS/GSM module with English or Specified language

With optional functions for use

Rated currents, System phase current,

Rated voltages, System phase voltage and secondary low voltage power supply voltage Frequency

power (kWh), reactive power (kVarh), power factor

With optional reclosing interval for user pre-program

reclosing times setting support

Dead time setting support

With events recording function

SOE 10000 operations record

Fault record and normal operation record

Note:mean should customized by manufacturer if needed

Environmental requirement

Maximum temperature:

+40°C

Minimum temperature:

-30°C

Monthly average humidity

95%

Humidity:

90%

Above sea level:

2500m or higher

Ambient air Not apparently polluted by corrosive and flammable gas, vapor

 

 

Reference Projects for outdoor vacuum recloser

  • Rockwill Ukraine 186 Units 12kV Outdoor Vacuum Recloser Project Success Case
    In response to the operational characteristics of Ukraine’s local power grid and targeting harsh high-latitude outdoor working conditions, we rely on core technologies of intelligent reclosing and self-healing to precisely adapt to the complex grid environment with frequent thunderstorms and drastic diurnal temperature variations, steadily promoting the automatic and intelligent upgrade of regional rural power grids and suburban distribution networks.01 Project Overview1.1 Project BackgroundIn 2
  • DTEK Grid Upgrade: Operation of Rockwill 10kV Smart Recloser in -40°C Extreme Cold Environment Ukraine Case Study
    As a benchmark for Chinese‑manufactured medium‑voltage distribution equipment going global, Rockwill established in‑depth cooperation with DTEK Kyiv Power Grid, Ukraine. Tailored outdoor vacuum recloser solutions were mass‑deployed to address existing weaknesses in local 10 kV distribution networks, comprehensively improving regional power supply reliability and automation to build a flagship distribution grid modernization project in Kyiv.01 Project Background: Core Pain Points of DTEK Kyiv Dis
  • Successful Case of 170 Sets of 11kV Automatic Recloser Project in Kenya
    Against the backdrop of quality upgrading for Kenya’s urban and rural power grids, 11kV auto-reclosers deliver reliable performance to suit local climates and grid conditions. It enables rapid fault isolation and efficient operation and maintenance, forming a core safeguard for the upgrading of Kenya’s urban and rural distribution networks.01 Project Overview1.1 Project BackgroundIn May 2023, 170 sets of 11kV Automatic Reclosers (Model: RCW12M) were officially supplied and applied to the medium-

Documentation Resource Library outdoor vacuum recloser

Rockwill Electric Group Profile
Public.
Rockwill Electric Group Profile
Brochure
English
15kV/27kV/38kV outdoor auto break vacuum recloser
Restricted.
15kV/27kV/38kV outdoor auto break vacuum recloser
Brochure
English
PDF
PDF
10 to 38kV auto vacuum break recloser Catalog
Restricted.
10 to 38kV auto vacuum break recloser Catalog
Catalogue
English
PDF
PDF
15kV automatic recloser technology specification
Public.
15kV automatic recloser technology specification
Technical Data
English

FAQ for outdoor vacuum recloser

Does Rockwill offer an MV Smart Auto Recloser capable of measuring primary currents as low as 0.1A?

Yes. In addition to the standard 2A–16,000A range, Rockwill provides custom-configured units for ultra-low current measurement and protection in the 0.1A–2A range.

How to select current sensor or current transformer specifications for Rockwill Smart Recloser?

The Rockwill standard smart recloser offers high precision with a wide measuring range (2A–16,000A). Simply ensure your normal current is within this standard range when making a selection.

What are the key differences between Rockwill's RCW single-phase vacuum recloser and a ZW32-type VCB?

While the ZW32 is a basic circuit breaker requiring an external controller, the RCW is a fully integrated smart grid recloser with built-in protection, sensors, and communication.

Furthermore, the RCW strictly complies with IEC 62271-111 and ANSI C37.60 standards, featuring premium insulation tailored for international distribution automation projects.

Does Rockwill single-phase vacuum recloser provide OEM/ODM services for local partners and regional manufacturers?

Yes, Rockwill provides comprehensive OEM/ODM programs for the RCW single-phase vacuum recloser. To maintain our high quality standards, we partner exclusively with regional manufacturers and distributors who possess robust engineering expertise and local service capabilities.

Our goal is to build strategic alliances that deliver not just premium hardware, but exceptional local technical support for smart grid modernization.

Why does the RCW single-phase vacuum recloser adopt 10,000 SOE event storage?

Distribution network faults occur occasionally with long data accumulation cycles. RCW single-phase vacuum reclosers are installed on overhead poles and may only encounter faults once every several months or years.

Conventional controllers can only store hundreds of records and old data will be overwritten by new events. The 10,000-point large-capacity SOE storage prevents the loss of early fault records, preserving complete time-sequenced event logs for later analysis.

Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Message
Inquiry
Email
E-mail
WhatsApp
WhatsApp
Chat
Chen/CEO