| Brand | ROCKWILL |
| Model NO. | YBM Series Prefabricated Substation for Residential Communities-6 to 40.5kV |
| Rated voltage | 40.5kV |
| Rated normal current | 630A |
| Rated frequency | 50/60Hz |
| Series | YBM |
The YBM series products represent a highly integrated power distribution solution, meticulously assembling medium-voltage (MV) switchgear, transformers, and low-voltage (LV) distribution equipment based on pre-defined connection schemes. Engineered for versatility, this series of substations is ideally suited for diverse applications, including residential communities, hotels, large-scale construction sites, and high-rise buildings.
It operates efficiently within voltage ranges of 6kV,12kV, 24kV and 40.5kV, at a frequency of 50Hz, and can handle capacities of up to 2500kVA.Adhering to stringent international standards, the YBM series complies with IEC 60076-1 and IEC 62271-202. It also meets the requirements of ANSI/IEEE C57.12.00, C57.12.20, and C57.12.90, as well as BS171 and SABS 780 (certification available upon request), ensuring reliable performance and quality assurance across various regions and industries.
| Item |
Unit | HV side | Transformer | LV side | |
|---|---|---|---|---|---|
| Rated voltage |
kV | 6、12、24、40.5kV | 6、12、24、40.5kV | 0.4 | |
| Rated current |
A | 630 | N/A | Less than 4000 | |
| Frequency |
Hz | 50/60 | |||
| Rated Capacity |
kVA | 50-2500 | |||
| 1min Power Frequency Withstand Voltage (kV) | Phase-to-phase | kV |
32、42、65 / 50、95 | 2.5 |
|
| Isolating distance | 32、48、79 / 60、110 | ||||
| BIL |
Phase-to-phase | 60、75、125 / 95、185 | 12 | ||
| Isolating distance | 60、85、145 / 115、215 | ||||
| IP Rating | IP43 | IP33D | IP43 | ||
| Appearance Dimensions |
mm | According to main wiring circuit diagram | |||
Both indoor or outdoor
Air temperature:
Maximum temperature: +40℃; Minimum temperature:-25℃
Humidity: Monthly average humidity 90%; Daily average humidity 95% .
Altitude above sea level: Maximum installation altitude: 2000m.
Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
No frequent violent shake
Both indoor or outdoor
Air temperature:
Maximum temperature: +40℃; Minimum temperature:-25℃
Humidity: Monthly average humidity 90%; Daily average humidity 95% .
Altitude above sea level: Maximum installation altitude: 2000m.
Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
No frequent violent shake
Note: Beyond those services condition should enquiry to manufacturer technical dept during order