| Brand | ROCKWILL |
| Model NO. | Customization Oil-immersed Three-Phase Transformer for Transmission Substation |
| Rated capacity | 150000kVA |
| Primary voltage | 242kV |
| Secondary voltage | 6.3kV |
| Methods of regulation | N/A |
| Winding type | Three Winding |
| Series | SFS(Z) |
This three-phase oil-immersed power transformer is designed for 220–245kV class high-voltage transmission substations, industrial power systems, and renewable energy grid connection. The core-type construction with grain-oriented silicon steel reduces no-load losses.
On-load tap-changing (OLTC) enables voltage regulation under load for stable grid operation. Manufactured and tested per IEC 60076-1, IEEE C57.12.00, ANSI C57.12.90, and AS/NZS 60076.5. Suitable for thermal power plants, large industrial bases, urban substations, and wind-solar renewable energy integration.
| Rated capacity | 240 MVA |
| Primary voltage | 230 kV |
| Secondary voltage | 6.3 kV |
| Regulation method | On-load tap-changing (OLTC) |
| Winding type | Double winding |
| Vector group | YNd11 |
| Impedance voltage | ≥12.5% |
| Tap range | ±8×1.25% |
| Cooling method | ONAF |
| Insulation level Um | 245 kV |
| LI / AC withstand | 950 kV / 395 kV |
| Frequency | 50/60 Hz |