| Brand | ROCKWILL |
| Series | ZGS |
| Rated primary voltage | 10-40.5 kV |
| Rated capacity | 100-2500kVA |
| Rated frequency | 50 / 60 Hz |
| Vector group | Dyn11 / Yyn0 / YNd11 |
What it is: An American-style prefabricated pad-mounted substation (ZGS Series) engineered for 10 kV to 40.5 kV medium-voltage underground distribution networks. It integrates a high-voltage load break switch, two-stage protective fuses, and an oil-immersed step-down transformer within a single compact, hermetically sealed oil tank, paired with segregated high- and low-voltage cable compartments.
Core ratings: High-voltage ratings 10 kV, 11 kV, 22 kV, 24 kV, 33 kV, 35 kV, 40.5 kV; low-voltage output 0.4 kV (400 V) / 480 V; transformer capacities from 100 kVA up to 2500 kVA; frequency 50 / 60 Hz; lightning impulse withstand level (BIL) up to 200 kV (for 40.5 kV class).
Operating configurations: Supports both Radial (Terminal) and Loop Feed (Ring Network) topologies via 2-position or 4-position oil-immersed load break switches, enabling continuous service during downstream cable maintenance.
Mechanism & Protection: Dual-fuse coordinated protection system: oil-immersed Bay-O-Net plug-in overload expulsion fuses paired in series with full-range current-limiting backup fuses (ELSP). High-voltage switching utilizes a spring-operated, quick-make/quick-break load break switch capable of interrupting full rated load current.
Construction: Fully sealed hermetic corrugated tank with nitrogen cushion or bellows expansion; tamper-resistant outdoor steel enclosure with multi-point latching, hidden hinges, and anti-vandalism padlock provisions. Ingress protection IP3X / IP54; ultra-low noise level ≤ 50 dB.
Monitoring & Safety: Comprehensive visual instrumentation including an oil temperature gauge with alarm contacts, magnetic oil level gauge, vacuum/pressure gauge, automatic pressure relief valve (PRV), and sampling/drain valves.
Environment: Outdoor concrete pad-mounted installation; standard ambient temperature -30 °C to +40 °C (extended -40 °C to +55 °C available); seismic withstand up to 0.3g; heavy pollution and salt-fog corrosion-resistant multi-stage electrostatic powder coating.
Commercial: Competitive factory direct pricing starting from $24,000.00 base depending on capacity, voltage tier, and LV feeder automation options. 24-hour RFQ response
Warranty: 10-year comprehensive unit warranty covering transformer active core and coil assembly, tank hermetic integrity, and high-voltage switching components. Includes complimentary engineering design support for protection coordination curves and single-line integration during tender/specification stages.
The ZGS Outdoor Prefabricated Pad-Mounted Transformer cuts substation civil works and footprint requirements by up to 60-70% compared to conventional European-style brick/containerized substations. By submerging the primary load break switch and fuses directly inside the dielectric cooling fluid of the transformer tank, it delivers a dead-front, tamper-proof underground distribution hub ideal for space-constrained urban, commercial, and renewable installations.
Conventional medium-voltage substations separate the switchgear, transformer, and low-voltage distribution into bulky multi-chamber enclosures. In contrast, the American-style pad-mounted design combines primary switching, primary overcurrent protection, and core-coil assembly into a common fluid-filled enclosure.
| Attribute | Specification |
|---|---|
| Series | ZGS Series |
| Device type | Outdoor Prefabricated Pad-Mounted Substation (American Style) |
| Rated primary voltage | 10 kV, 11 kV, 22 kV, 24 kV, 33 kV, 35 kV, 40.5 kV |
| Rated secondary voltage | 0.4 kV, 0.415 kV, 0.48 kV (Customizable) |
| Rated capacity | 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 kVA |
| Rated frequency | 50 / 60 Hz |
| Vector group | Dyn11 / Yyn0 / YNd11 |
| Primary connection | Loop feed (Ring) or Radial (Terminal) |
| HV switchgear | Oil-immersed load break switch (2-position or 4-position, 630A) |
| Primary protection | Bay-O-Net expulsion fuse + Backup current-limiting fuse (ELSP) |
| Cooling method | ONAN (Mineral oil or natural ester / FR3 biodegradable fluid) |
| Lightning impulse withstand (BIL) | 75 kV (12kV class), 125 kV (24kV class), 170 kV (33kV class), 200 kV (40.5kV class) |
| Power frequency withstand voltage | 28 kV / 42 kV / 70 kV / 85 kV (1 min dry) |
| Audible noise level | ≤ 48 - 52 dB(A) |
| Enclosure ingress protection | IP3X standard; IP54 / IP55 customizable |
| Service life | 30+ years under continuous outdoor utility loading |
| Tank sealing | Hermetically sealed corrugated tank (welded cover / bolted with nitrile gaskets) |
| Standards | IEC 60076-1, IEEE C57.12.00, IEEE C57.12.28 |
The ZGS series operates as a self-contained, pad-mounted step-down transformation and distribution substation. It receives 10 kV to 40.5 kV underground cable power, routes it through an internal multi-position oil-immersed load break switch and coordinated dual fuses, steps the voltage down to 0.4 kV, and feeds multiple low-voltage feeder circuits equipped with metering, MCCB protection, and optional power factor correction.
"Pad-mounted distribution transformers installed in public and semi-public access environments require tamper-resistant, dead-front construction with zero exposed live parts and verified enclosure integrity to withstand environmental and unauthorized physical intrusion."
— Authority: IEEE C57.12.28 (Standard for Pad-Mounted Equipment - Enclosure Integrity) and IEC 62271-202 (High-voltage/Low-voltage prefabricated substation)
ROCKWILL Engineering Response: Rockwill ZGS pad-mounted transformers feature recessed security locking, concealed heavy-duty stainless steel hinges, baffled ventilation louvers, and certified dead-front elbow connections, ensuring absolute public safety in dense urban and residential zones.
By utilizing the dielectric insulating oil as both the cooling medium for the active transformer core and the arc-quenching medium for the load break switch and backup fuses, overall exterior dimensions are slashed to approximately one-third of conventional European compact substations of identical capacity.
The transformer features an external-accessible Bay-O-Net expulsion fuse operating in series with an internal oil-immersed current-limiting backup fuse (ELSP):
The tank is fabricated from high-grade structural steel with continuous welding, hermetically sealing the insulation fluid against oxidation and moisture ingress. Real-time condition monitoring is provided by:
Optimized core clamping structures, high-permeability grain-oriented silicon steel laminations, and precision step-lap mitered joints suppress magnetostrictive vibration, keeping operating sound levels strictly below 50 dB(A).
Certified Rockwill factory ratings cover primary distribution classes from 10 kV up to 40.5 kV, with rated capacities ranging from 100 kVA to 2500 kVA (3150 kVA available on custom order). Configurations include dead-front radial or loop feed layouts, with low-voltage compartments fully tailored for utility revenue metering, multi-circuit MCCB distribution, and intelligent SCADA telemetry.
| Parameter | Unit | 10kV - 12kV Class | 24kV Class | 33kV - 35kV Class | 40.5kV Class |
|---|---|---|---|---|---|
| Rated primary voltage | kV | 10 / 11 / 12 | 20 / 22 / 24 | 33 / 34.5 / 35 | 38.5 / 40.5 |
| Rated secondary voltage | kV | 0.4 / 0.415 / 0.48 | 0.4 / 0.415 / 0.48 | 0.4 / 0.415 / 0.48 | 0.4 / 0.415 / 0.48 |
| Rated capacity range | kVA | 100 - 2500 | 100 - 2500 | 200 - 2500 | 315 - 2500 |
| Frequency | Hz | 50 / 60 | 50 / 60 | 50 / 60 | 50 / 60 |
| BIL (Lightning impulse) | kV | 75 / 95 | 125 | 170 | 200 |
| Power frequency withstand | kV | 28 / 35 | 50 | 70 | 85 |
| Impedance voltage (Uk) | % | 4.0 - 5.5 | 4.5 - 6.0 | 5.5 - 6.5 | 6.0 - 7.0 |
| Audible noise level | dB(A) | ≤ 48 | ≤ 50 | ≤ 52 | ≤ 54 |
| Tap changer range | % | ±2×2.5% / ±5% | ±2×2.5% / ±5% | ±2×2.5% / ±5% | ±2×2.5% / ±5% |
| Parameter | Type | Functional Description |
|---|---|---|
| Primary Feed Topology | Radial (Terminal) | Single cable infeed with 2-position on/off load break switch |
| Primary Feed Topology | Loop Feed (Ring Network) | Dual cable infeed (Loop A / Loop B) with 4-position T-type or V-type load break switch |
| Load Break Switch Rating | 630 A continuous | 630 A load interrupt, 16 kA / 20 kA fault-make capability (3 operations) |
| HV Bushings | Dead-front / Live-front | 200A well bushings / 600A apparatus bushings conforming to IEEE 386 |
| Tap Changer | De-energized tap changer (NLTC) | 5-position or 7-position rotary switch operable from HV compartment |
| Parameter | Standard Specification | Optional Heavy-Duty Tier |
|---|---|---|
| Tank steel sheet thickness | ≥ 4.0 mm carbon structural steel | 304 or 316L stainless steel tank |
| Surface treatment | Zinc-rich epoxy primer + Electrostatic polyester powder | Marine-grade C5-M polyaspartic coating |
| Standard coating color | Munsell 7GY 3.29/1.5 (Pad-mount Green) or Light Grey (RAL 7035) | Custom RAL colors per utility spec |
| Cabinet doors & locks | Captive penta-head security bolt + padlockable handle | Dual interlocking doors with door stays |
| Ingress protection rating | IP3X (Ventilated compartment) / IP54 (Sealed compartments) | IP55 / IP65 weather-sealed construction |
Rockwill ZGS transformers deploy a time-proven two-tier coordinated protection architecture. The expulsion fuse (Bay-O-Net) handles common distribution transformer overloads and low-level secondary fault currents, while the current-limiting backup fuse (ELSP) limits prospective catastrophic short-circuit currents up to 50 kA, safeguarding personnel, the environment, and upstream equipment.
As cited in [IEEE C57.12.00 & IEEE C37.47 (Standard for High-Voltage Current-Limiting Fuses)]:
"Full-range protection of fluid-immersed pad-mounted transformers requires coordinating thermal-sensing expulsion elements with high-interrupting current-limiting backup elements to prevent tank overpressurization under low-impedance core faults."
The Rockwill ZGS dual-fuse system strictly coordinates the melt curves so that the Bay-O-Net fuse always operates first on overloads, and the current-limiting fuse only intervenes during severe primary short circuits.
| Protective Device | Location | Function & Operating Characteristic |
|---|---|---|
| Bay-O-Net Expulsion Fuse | HV Tank Wall (Draw-out tube) | Protects against sustained thermal overloads (1.5 - 3x rated current) and secondary phase-to-ground faults. Draw-out replacement in minutes. |
| ELSP Current-Limiting Fuse | Submerged inside oil tank | High-speed clearance (sub-cycle < 5 ms) of high short-circuit currents up to 50 kA. Suppresses I2tI2t let-through energy. |
| HV Load Break Switch | Submerged inside oil tank | 3-phase gang-operated spring toggle mechanism. Capable of interrupting rated 630A full load current and charging currents. |
| Pressure Relief Valve (PRV) | Tank cover / upper sidewall | Automatically opens at 35 kPa (5 psi) to relieve tank pressure surges; auto-reseals at 20 kPa with visual indicator ring. |
| Mechanical Interlocking | Compartment doors | HV compartment door cannot be opened until LV compartment door is unlocked and opened. |
Built in hermetically sealed corrugated tanks with multi-barrier powder-coated enclosures, Rockwill ZGS pad-mounted transformers operate reliably from -30 °C to +40 °C (extended -40 °C to +55 °C package), at altitudes up to 3,000 meters with certified insulation creepage, and in severe coastal salt-spray zones with optional 304/316 stainless steel enclosures.
"Equipment installed in outdoor public environments must withstand solar radiation, condensation, extreme thermal cycling, and aggressive chemical contaminants without structural degradation or loss of dielectric strength."
— Authority: IEC 60076-1 and IEEE C57.12.28 (Enclosure Coating Integrity)
Rockwill verifies all exterior coatings through 1,000-hour ASTM B117 salt spray tests and 500-hour accelerated QUV weathering tests, preventing surface chalking and under-film rust creepage.
| Environmental Parameter | Standard Value | Extended Utility / Industrial Tier |
|---|---|---|
| Ambient operating temperature | -30 °C to +40 °C | -40 °C to +55 °C (Low-temperature oil / FR3 ester fluid) |
| Maximum installation altitude | ≤ 1,000 m | Up to 3,000 m (custom BIL derating compensation) |
| Foundation load capacity | ≥ 100 kPa | Pad-mounted on reinforced concrete slab |
| Grounding resistance | ≤ 4 Ω | Dual internal copper grounding pads with external M12 terminals |
| Solar radiation resistance | Global standard (1,000 W/m²) | Double-walled heat-insulated roof shield |
| Seismic acceleration | Horizontal 0.3g, Vertical 0.15g | Heavy seismic qualification up to 0.5g (IEEE 693) |
| Relative humidity | Up to 95% at 25 °C (non-condensing) | 100% tropical condensing duty |
Utilities and EPC contractors can obtain a formal technical proposal, detailed single-line diagram (SLD), and preliminary dimensional drawing within 24 hours by submitting primary/secondary voltages, rated kVA capacity, loop or radial feed preference, and low-voltage distribution requirements. Rockwill provides complimentary protection curve coordination and loss evaluation studies during project specification stages.
Depending on the configuration selected:
| Cost Driver | Effect on Price | Engineering Decision Factors |
|---|---|---|
| Transformer capacity (kVA) | Baseline pricing scale | 100 kVA to 2500 kVA ratings |
| High-voltage rating tier | +10% to +35% | 11kV/24kV standard vs. 33kV/40.5kV high-BIL designs |
| Core loss tier | +5% to +20% | Standard IEC/IEEE losses vs. Tier-2 ultra-low loss silicon steel or amorphous metal |
| Cooling dielectric fluid | +8% to +15% | High-grade mineral oil vs. Biodegradable FR3 natural ester fluid |
| Tank and cabinet material | +15% to +45% | Carbon steel + powder coat vs. 304/316L stainless steel enclosure |
| LV automation & metering | Variable per spec | Basic MCCBs vs. Smart multi-function meters, ATS, and RTU telemetry |
The figures above are indicative budget guidance for tender planning, not a binding offer. Definitive pricing depends on final technical specifications, project quantities, and delivery schedules.
To receive a binding, technically verified quotation within 24 hours, provide:
Engineering support for fuse-to-breaker protection coordination and foundation civil layout is provided free of charge during the project engineering phase.
Yes. The unit features an external-accessible Bay-O-Net expulsion fuse holder mounted on the high-voltage tank wall. Operators can easily replace the fuse cartridge on-site using a standard insulated hotstick in under 10 minutes without opening the main tank or draining transformer oil, minimizing maintenance downtime and preventing insulation contamination.
All units are designed, manufactured, and routine-tested in strict compliance with IEC 60076 and IEEE C57.12.00 / IEEE C57.12.28 (pad-mounted enclosure integrity).
Factory routine test reports (including winding resistance, voltage ratio, impedance, load/no-load losses, and dielectric insulation withstand) are provided with every shipment. Third-party type-test reports are available upon request.
Rockwill ZGS pad-mounted transformers support primary voltages from 10 kV up to 40.5 kV (including 11 kV, 22 kV, 24 kV, 33 kV, and 35 kV) and transformer capacities from 100 kVA up to 2500 kVA (customizable up to 3150 kVA).
We offer both radial (terminal) and loop feed (ring network) arrangements, customizable vector groups (Dyn11/Yyn0), and tailor-made low-voltage feeder compartments with required MCCB brands, metering, and smart RTU/FTU automation.