| Brand | ROCKWILL |
| Series | JDS |
| Rated voltage | 24 kV |
| Rated neutral current | Up to 3000 A |
| Rated frequency | 50 / 60 Hz |
Fault withstand time is the maximum duration an earthing transformer can endure fault-current thermal and mechanical stresses under rated short-time capacity, with standard durations of 10s, 30s, 60s, or 1 hour per IEEE 32/IEC 60076‑5. Selection must ensure withstand time ≥ protection clearing time plus redundancy—e.g., a 15‑second relay trip requires a 30‑second withstand rating to prevent damage.