Product Overview
Model: DC(B)-315~2500.Main application fields: static excitation systems of hydropower plants, thermal power plants, and ultra-large capacity nuclear power plants.
Product superiority
Developed as a high-performance product to meet the demands of power plant static excitation systems. This product series adopts a single-phase structure design, supporting high-voltage isolated phase-segregated bus inlets, and shielding between high-voltage and low-voltage windings, suitable for the static excitation systems of hydropower plants, thermal power plants, and nuclear power plants.
Performance Features
| Feature |
Description |
| Application |
Static excitation systems for hydropower, thermal power & nuclear power plants |
| Core Material |
High-quality cold-rolled grain-oriented silicon steel, 45° full mitered joint, resin-sealed surface |
| Winding |
HV: epoxy resin vacuum cast; LV: copper foil; HV/LV shielding (Faraday cage) |
| Low Partial Discharge |
≤ 5 pC (at 1.1 Ur/√3 for 1 min) |
| High Overload Capacity |
150% rated current for 60 s; up to 200% short-time (Class H insulation) |
| Strong Short-circuit Withstand |
Short-circuit impedance imbalance < 1%; high mechanical strength |
| Flame Retardant |
Self-extinguishing epoxy resin, no fire/explosion risk |
| Low Noise |
3–5 dB below national standard; optimized magnetic flux density design |
| Harmonic Suppression |
Faraday shielding layer between HV/LV to suppress harmonic overvoltage |
| Environmental Resistance |
Moisture-proof, dust-proof, salt-fog resistant; suitable for harsh environments |
| Maintenance Free |
No oil, no leakage, self-cleaning winding surface |
Technical Parameters
| Parameter |
Specification |
| Model Series |
DC(B), ZLSC, ZSC(B) |
| Phase |
Single-phase (large units) / Three-phase |
| Rated Capacity |
315 – 2,500 kVA (excitation type); 20 – 5,000 kVA (rectifier type) |
| HV Voltage Level |
10 kV, 13.8 kV, 15.75 kV, 20 kV, 22 kV |
| LV Voltage |
0.4 kV, 0.66 kV, 0.69 kV (customizable) |
| Frequency |
50 Hz / 60 Hz |
| Tap Range |
±2×2.5% or ±5% (off-circuit tap changer) |
| Vector Group |
Dyn11, Yyn0, Dd0, Yd11 (customizable) |
| Insulation Class |
Class F (155 °C) / Class H (180 °C) |
| Cooling Mode |
AN / AF |
| No-load Loss |
≤ 0.5% of rated capacity |
| Load Loss |
≤ 1.5% of rated capacity |
| No-load Current |
0.5 – 1.6% |
| Short-circuit Impedance |
4%, 6%, 8% (varies by capacity) |
| Impedance Imbalance |
< 1% |
| Noise Level |
≤ 65 dB (capacity-dependent) |
| Lightning Impulse Withstand |
75 kV (10 kV class) |
| AC Withstand Voltage |
28 kV / 3 kV (HV/LV) |
| DC Bias Tolerance |
≤ 1.5% of rated current |
| Rectifier Pulse Number |
6-pulse (THDi ≈ 25%); 12/24-pulse (THDi < 7%) |
| Altitude |
≤ 1,000 m (derated above) |
| Ambient Temperature |
–25 °C ~ +40 °C |
| Protection Class |
IP00 / IP20 / IP23 |
| Winding Material |
Copper (standard) / Aluminum (optional) |
Typical Capacity–Loss Reference (10 kV Class, F-Class)
| Rated Capacity (kVA) |
No-load Loss (W) |
Load Loss @ 120 °C (W) |
No-load Current (%) |
Impedance (%) |
| 315 |
~ 750 |
~ 3,500 |
1.2 |
4.0 |
| 500 |
~ 1,050 |
~ 5,100 |
1.0 |
4.0 |
| 630 |
~ 1,250 |
~ 6,200 |
0.9 |
6.0 |
| 800 |
~ 1,500 |
~ 7,500 |
0.8 |
6.0 |
| 1000 |
~ 1,750 |
~ 9,200 |
0.7 |
6.0 |
| 1250 |
~ 2,100 |
~ 11,000 |
0.7 |
6.0 |
| 1600 |
~ 2,500 |
~ 13,500 |
0.6 |
6.0 |
| 2000 |
~ 2,900 |
~ 16,200 |
0.6 |
8.0 |
| 2500 |
~ 3,400 |
~ 19,500 |
0.5 |
8.0 |
Applicable Standards (Simplified)
| Type |
Standard |
Purpose |
| International |
IEC 60076 |
Power transformers (general) |
| International |
IEC 61378 |
Transformers for industrial applications (rectifier/convertor) |
| China |
GB 1094 series |
Power transformers (general) |
| China |
GB/T 10228 |
Dry-type power transformer parameters |
| China |
GB/T 18494 |
Convertor transformers (specialized) |
| USA |
IEEE C57.12 |
Standard for transformers |