| Brand | ROCKWILL |
| Series | RHB |
| Rated voltage | 252kV-550kV |
| Rated current | up to 5000 A |
| Rated short-time withstand current | up to 63 |
| Rated peak withstand current | up to 158 |
RHB-252
| Item | Unit | Parameter |
|---|---|---|
| Rated voltage | kV | 252 |
| Rated frequency | Hz | 50/60 |
| Rated current | A | up to 5000 |
| Rated short-time withstand current, up to 3 s | kA | up to 63 |
| Rated peak withstand current | kA | up to 158 |
| Rated short-duration power-frequency withstand voltage, 1 min | kV | 460 |
| Power-frequency withstand voltage, 1 min across open contacts | kV | 530 |
| Rated lightning impulse withstand voltage, 1.2/50 μs | kV | 1050 |
| Rated lightning impulse withstand voltage, 1.2/50 μs, across open contacts | kV | 1200 |
| Rated filling pressure (abs. at 20 ℃) circuit-breaker | MPa | 0.6 |
| Minimum functional pressure (abs. at 20 ℃) circuit-breaker | MPa | 0.5 |
| Temperature range (ambient) | ℃ | -30~+40 |
| Type of installation | — | outdoor |
| Partial discharge | pC | <5 |
| Annual SF₆ leakage rate | — | <0.5% |
| Maintenance cycle | Year | 30 |
RHB-420
| Item | Unit | Parameter |
|---|---|---|
| Rated voltage | kV | 420 |
| Rated frequency | Hz | 50/60 |
| Rated current | A | up to 5000 |
| Rated short-time withstand current, up to 3 s | kA | up to 63 |
| Rated peak withstand current | kA | up to 158 |
| Rated short-duration power-frequency withstand voltage, 1 min | kV | 740 |
| Power-frequency withstand voltage, 1 min across open contacts | kV | 850 |
| Rated lightning impulse withstand voltage, 1.2/50 μs | kV | 1425 |
| Rated lightning impulse withstand voltage, 1.2/50 μs, across open contacts | kV | 1550 |
| Rated filling pressure (abs. at 20 ℃) circuit-breaker | MPa | 0.6 |
| Minimum functional pressure (abs. at 20 ℃) circuit-breaker | MPa | 0.5 |
| Temperature range (ambient) | ℃ | -30~+40 |
| Type of installation | — | outdoor |
| Partial discharge | pC | <5 |
| Annual SF₆ leakage rate | — | <0.5% |
| Maintenance cycle | Year | 30 |
RHB-550
| Item | Unit | Parameter |
|---|---|---|
| Rated voltage | kV | 550 |
| Rated frequency | Hz | 50/60 |
| Rated current | A | up to 5000 |
| Rated short-time withstand current, up to 3 s | kA | up to 63 |
| Rated peak withstand current | kA | up to 158 |
| Rated short-duration power-frequency withstand voltage, 1 min | kV | 830 |
| Power-frequency withstand voltage, 1 min across open contacts | kV | 950 |
| Rated lightning impulse withstand voltage, 1.2/50 μs | kV | 1675 |
| Rated lightning impulse withstand voltage, 1.2/50 μs, across open contacts | kV | 2125 |
| Rated filling pressure (abs. at 20 ℃) circuit-breaker | MPa | 0.6 |
| Minimum functional pressure (abs. at 20 ℃) circuit-breaker | MPa | 0.5 |
| Temperature range (ambient) | ℃ | -30~+40 |
| Type of installation | — | outdoor |
| Partial discharge | pC | <5 |
| Annual SF₆ leakage rate | — | <0.5% |
| Maintenance cycle | Year | 30 |
Note:RHB platform is fully scalable to accommodate a wide voltage spectrum ranging from 11kV to 550kV. We specialize in engineering bespoke solutions for challenging environments, including high-altitude, seismic zones, and heavy pollution areas. Please consult our technical team for tailored designs that precisely match your grid's unique requirements.
RHB-245

Ambient temperature: -30℃~+40℃
Altitude: <1000m
Max wind speed: <34m/s
Daily temperature variation: <25℃
Solar irradiance: <0.1W/cm²
Monthly average RH: <90%
Ice coating: <10mm
Seismic resistance: Horizontal<0.2g, Vertical<0.1g
Mounting: Outdoor
We stand firmly behind the quality and durability of our equipment. The RHB Series comes with a comprehensive 20-year warranty. This extended coverage reflects our confidence in the product's robust porcelain construction and long-term reliability, ensuring peace of mind for your long-term infrastructure investment.
The self-blast arc extinction technology significantly enhances mechanical efficiency by utilizing the energy from the arc itself to extinguish the current. This design drastically reduces the operating power required by the spring mechanism. Consequently, it lowers the mechanical stress on components, extends the service life of the breaker, and reduces the frequency of maintenance interventions, leading to lower overall operational costs.
Yes, the RHB platform is engineered for versatility. While our standard service conditions cover typical environments, we specialize in customizing solutions for challenging locations. We can adjust insulation levels for high-altitude sites and reinforce the mounting structure to withstand higher seismic intensities, ensuring stable performance regardless of the geographical challenges.
The RHB Series utilizes an interconnected gas chamber system across all three poles within a unified porcelain structure. This integrated design not only ensures synchronized operation but also simplifies the gas monitoring process. With a single high-precision pointer density relay managing the system, maintenance personnel can quickly verify the insulation status of the entire unit, reducing inspection time and complexity.
Absolutely. Understanding the dynamic nature of renewable energy integration, we offer flexible customization for control logic. Whether your project requires specific auto-reclosing sequences for wind farm stability or specialized synchronization protocols for solar stations, our engineering team can tailor the control cabinet logic to seamlessly interface with your specific grid management systems.