| Brand | ROCKWILL |
| Series | RHB |
| Rated voltage | 252kV |
| Rated current | up to 5000A |
| Rated peak withstand current | up to 158 kA |
| Rated frequency | 50/60 HZ |
Self-blast Arc Extinguishing Structure:Double-action arc-quenching chamber guarantees stable breaking performance under various load and fault current conditions.
Low Drive Power & Long Mechanical Life:Small required operating work; mechanical service life reaches over 10,000 switching cycles for long-term outdoor running.
High-performance Integral Arc Contact:Integral sintered copper-tungsten arc contact features excellent high-temperature resistance and anti-ablation capacity, capable of enduring more than 20 rated short-circuit breaking cycles.
Excellent Air-tightness & Insulation Performance:Precision sealing design ensures annual SF₆ leakage rate<0.5%; strict internal drying treatment keeps gas moisture far below standard requirement; specific creepage distance above 31mm/kV for superior outdoor anti-pollution insulation.
Premium Interrupter Raw Materials:Lightweight zinc alloy valve sheet stabilizes internal airflow; imported PTFE composite nozzle greatly improves arc ablation resistance and reliable arc extinction.
High-quality Matching Parts:Pointer-type SF₆ density relay and secondary electrical components adopt well-known joint-venture/imported brands for stable on-line gas monitoring and high running reliability.
High-strength Spring Operating Mechanism:Core structural parts made of high-strength forged alloy steel with good wear resistance, low failure rate under frequent operation.
| Rated voltage | kV | 252 |
| Rated frequency | Hz | 50/60 |
| Rated current | A | up to 5000 |
| Rated short-time withstand current, up to 3 s | kA | up to 63 |
| Rated peak withstand current | kA | up to 158 |
| Rated short-duration power-frequency withstand voltage, 1 min | kV | 460 |
| Power-frequency withstand voltage, 1 min across open contacts | kV | 530 |
| Rated lightning impulse withstand voltage, 1.2/50 μs | kV | 1050 |
| Rated lightning impulse withstand voltage, 1.2/50 μs, across open contacts | kV | 1200 |
| Rated filling pressure (abs. at 20 ℃) circuit-breaker | MPa | 0.6 |
| Minimum functional pressure (abs. at 20 ℃) circuit-breaker | MPa | 0.5 |
| Temperature range (ambient) | ℃ | -30~+40 |
| Type of installation | — | outdoor |
| Partial discharge | pC | <5 |
| SF₆ annual leakage rate | — | <0.5% |
| Maintenance cycle | Year | 30 |
Note:Beyond the standard 252kV specifications listed above, our manufacturing capabilities extend across a comprehensive voltage range from 40.5kV to 550kV. We offer flexible engineering solutions to customize insulation levels and breaking capacities, ensuring the equipment perfectly matches diverse grid requirements and unique project environments.


Circuit breaker model & specification
Rated electrical parameters: rated voltage, rated current, short-circuit breaking current
Service ambient condition: ambient temperature, installation altitude, pollution grade
Control parameters: energy storage motor voltage, opening/closing coil rated voltage
Primary terminal wiring direction
Spare parts and special tools (ordered separately as required)
Absolutely. We provide a full set of English technical manuals, including wiring diagrams and maintenance guides. We also maintain a stock of critical spare parts (such as arc contacts, nozzles, and sealing rings) to support the equipment throughout its 30-year maintenance cycle.
We offer comprehensive lifecycle support. This includes providing detailed outline dimension drawings for civil engineering planning, remote technical guidance for wiring (such as motor and coil voltage configurations), and on-site supervision if required to ensure the breaker is installed correctly according to the "Order Instruction" parameters.
Yes, as a specialized manufacturer, we provide extensive OEM/ODM services. While the RHB-252kV is a standard model, our production capabilities cover a wide voltage range from 40.5kV to 550kV. We can customize insulation levels, breaking capacities, and even branding to fit your specific project requirements and local grid standards.
Yes. The unit features a specific creepage distance of no less than 31mm/kV and utilizes precision sealing technology that limits the annual SF6 leakage rate to <0.5%. Combined with strict internal drying treatments, these features ensure superior insulation and anti-pollution performance even in harsh outdoor environments.
It utilizes a high-strength spring operating mechanism where core structural parts are made of forged alloy steel. This design offers excellent wear resistance and ensures a low failure rate, making it highly suitable for applications requiring frequent operation without compromising mechanical integrity.