| Brand | ROCKWILL |
| Series | RVD |
| Rated voltage | 72.5kV |
| Rated frequency | 60 Hz |
| At lightning impulse | 350kV |
| Rated normal current | 1200/2000/3000 A |
| Rated short-circuit making current | 100 kA |
Rockwill Group is a leading high-tech enterprise in China, specializing in the R&D, manufacturing, and sales of medium- and high-voltage switchgear and components for over 20 years. Following Pinggao Electric, XD Group, and XJ Electric, Rockwill Group is one of the few domestic manufacturers in China that has independently mastered the core technology of 72.5kV SF₆-free dead tank circuit breakers and successfully commercialized the product.
Based on this expertise, we have developed an SF₆-free dead tank circuit breaker (DTCB) that is very similar to its SF₆ predecessor. Using our g³ insulating and switching SF₆-free technology, the new RVD-72.5 remains compact with the same footprint. Performance and life cycle costs remain similar while offering a significant decrease in the carbon footprint.
The SF₆-free gas mixture used in the new RVD-72.5 works on the same well-known principle for insulation and breaking purposes as that of SF₆ gas. The g³ gas is a mixture of carbon dioxide (CO₂) with oxygen (O₂) and a small percentage of an additive (C4F7N), whose physical properties are essential to g³. Its contribution to global warming is significantly lower than that of SF₆ gas – reduced by 99%.
| IEC | VALUE | UNITS |
|---|---|---|
| Rated voltage | 72.5 | kV |
| Rated frequency | 60 | Hz |
|
Rated insulation level
|
160 | kV |
| 140 | kV | |
| At lightning impulse | 350 | kV |
| Rated normal current | 1200/2000/3000 | A |
| Rated short-circuit breaking current | 40 | kA |
| Rated short-circuit making current | 100 | kA |
| Rated break time | 50 | ms |
| Rated operating sequence | O-CO-15s-CO O-0.3s-CO-180s-CO |
|

| Ambient air temperature upper limit | +40 °C |
| Ambient air temperature 24-hour average | +35 °C |
| Ambient air temperature lower limit | –30 °C |
| Altitude above sea level | ≤ 1000 m |
| Relative humidity (24-hour average) | ≤ 95% |
| Relative humidity (monthly average) | ≤ 90% |
| Water vapor pressure (24-hour average) | ≤ 2.2 kPa |
| Water vapor pressure (monthly average) | ≤ 1.8 kPa |
| Solar radiation | ≤ 1000 W/m² |
| Pollution level | Level III |
| Seismic capability | High seismic per IEEE 693 |
Similar to SF₆ breakers — sealed-for-life gas system, factory-assembled and tested before shipment, low maintenance frequency.
Yes. The RVD-72.5 shares the same dead-tank footprint and many components with the RHD-72.5 SF₆ breaker, with identical operational and maintenance procedures, enabling direct retrofit.
It uses g³ gas — a mixture of CO₂, O₂ and a small percentage of C4F7N additive. It contains no SF₆ and reduces global warming potential by 99% versus SF₆.