| Brand | ROCKWILL |
| Series | RVD |
| Rated voltage | 145kV |
| Rated frequency | 60Hz |
| Rated normal current | 3000 A |
| Rated break time | 50 ms |
| Rated short-circuit breaking current | 63kA |
The RVD-145 Dead Tank Vacuum Circuit Breaker, launched by ROCKWILL, is a gas-insulated switchgear with a voltage rating of up to 145 kV. Its core features include the use of clean air as the insulation medium combined with vacuum interruption technology, aiming to achieve zero greenhouse gas emissions and zero global warming potential in power transmission.
Eco-Friendly Technology, Zero Environmental Impact:
Safe and Reliable, Zero Health Risks
Simple Operation, Zero Regulatory Burden
Excellent Performance, Zero Compromise
| Item | Parameters |
|---|---|
| Rated voltage | 145kV |
| Rated frequency | 50/60Hz |
| Rated short‑duration power‑frequency withstand voltage (1 min) | 275kV |
| Rated lightning impulse withstand voltage (1.2/50 us) | 650kV |
| Rated continuous current‑ bus bar / feeder bus coupler | 3150A |
| Rated short‑circuit breaking current | 50kA |
| Rated peak withstand current | 135kA |
| Rated short‑time withstand current (up to 3 s) | 50kA |
| Leakage rate per year and gas compartment (type tested) | <0.1% |
| Drive mechanism of circuit‑breaker | stored energy spring |
| Rated operating sequence | 0‑0.3 s‑C0‑3 min‑CO
|
| interrupter technology | vacuum |
| Insulation medium | clean air |
| Weight of SF6 or other fluorinated green‑house gases | 0 kg |
| Rated filling pressure | 0.8 MPa (abs.) |
| Bay width common pole drive | 1000 mm |
| Bay height depth (depending on bay arrangement) | 3.200/5,500 mm |
| Bay weight (depending on bay arrangement) | 6.0t |
| Ambient temperature range | -50°C +55°C |
| Installation | Indoor/outdoor |
| First major inspection | > 25 years |
| Expected lifetime | > 50 years |
| Standards | IEC/IEEE |

| RATED MAX. VOLTAGE | 145 kV |
|---|---|
| A (in/mm) | 89.2/2264 |
| B (in/mm) | 73.85/1876 |
| C (in/mm) | 122.9/3120 |
| D (in/mm) | 167.5/4254 |
| E (in/mm) | 51.83/1316 |
| F (in/mm) | 137.4/3490 |
| G (in/mm) | 65.9/1674 |
| H (in/mm) | 107.85/2739.5 |
| I (in/mm) | 97.5/2476 |
| J (in/mm) | 51.83/1316 |
| Air temperature | Maximum temperature: +55℃; |
| Minimum temperature: -50℃ | |
| Humidity | Daily average humidity 100%. |
| Above sea level | Maximum installation altitude: 1000m. |
Yes, we can supply full type test certificates and support third-party witness testing as required for your substation project.
No. Interruption takes place inside the vacuum interrupter, no toxic decomposition substances will be produced. The medium is non-toxic and can be directly vented at end-of-life.
The RVD-145 dead tank vacuum circuit breaker adopts clean air as insulation medium together with vacuum interruption technology, free of SF₆ and any F-gases, with zero GWP.