占位边距

Oil-immersed Automatic Step Voltage Regulator OEM China 7.62 kV-34.5 kV

  • Oil-immersed Automatic Step Voltage Regulator OEM China 7.62 kV-34.5 kV

Key attributes

Brand ROCKWILL
Series RVR-1
Rated Voltage 7.62-34.5kV
Rated Current 50-546A
Capacity 38-660kV
Rated Frequency 50/60 Hz

Description

The RVR-1 single-phase automatic voltage regulator from China manufacturer Rockwill is a tap-changing autotransformer designed for medium-voltage overhead distribution networks, compliant with IEEE C57.12.It realizes stable line voltage regulation covering a ±10% boost & buck range via 32 fine adjustment steps, each delivering approximately 0.625% voltage correction.

It supports voltage grades from 2400V (60kV BIL) up to 34,500V (200kV BIL), compatible with both 50Hz and 60Hz global power grids. All units are fitted with internal potential winding taps and an external ratio correction transformer, allowing one regulator model to adapt to multiple system voltage levels flexibly.

Two installation configurations are available: Smaller kVA models are equipped with pole-mount support lugs and anchoring fittings for platform/substation installation; large-capacity units come with integrated heavy-duty substation bases for pad-mounted ground deployment.

Product Showcase Video

Outline Drawing

Single Phase Automatic Voltage Regulator Outline Drawing

Core Product Advantages

  • Ultra-Precise Voltage Regulation:32 loaded tap steps provide fine voltage correction across the full ±10% buck-boost range, stabilizing grid voltage fluctuations and guaranteeing consistent power quality for downstream loads.
  • Extended Mechanical Service Lifespan:The proprietary arc-suppression tap switch design eliminates electric arcing during tap shifting, supporting up to 1 million mechanical operation cycles for long-term stable performance.
  • Minimal Maintenance with 20-Year Design Life:Adopts fully sealed oil-immersed tank structure with high weatherproof protection rating, delivering outstanding resistance to UV radiation, humidity and salt spray. It enables long-term outdoor maintenance-free operation with a certified 20-year design service life.
  • Ultra-Low Energy Losses:Optimized single-phase magnetic core structure greatly reduces iron loss and no-load power consumption, with the total loss of the whole unit controlled below 0.1% for superior energy efficiency.
  • Strong Overload Tolerance:Rated with a 55°C temperature rise design; it can continuously withstand 12% overload under 65°C temperature rise to cope with peak load surges on distribution lines.

 Technical Specification Table

Voltage (kV) Current (A) Capacity (kVA) BIL (kV) Power Frequency Withstand Voltage (kV) Insulation Class
7.62 50 38 60/75 20 A
100 76
150 114
219 167
328 250
438 333
546 416
13.8 50 69 95/125 38
100 138
150 207
200 276
300 414
400 552
14.4 50 72
100 144
200 288
300 432
400 576
19.92 50 100 170/200 70
100 200
167 333
200 400
335 667
34.5 50 165
100 330
150 495
200 660

Product Finished Display Photo

Single Phase Automatic Voltage Regulator Product Finished Display Photo

RVR-1 Automatic Step Voltage Regulator On-site Operation Photo

The RVR-1 pole-mounted automatic step voltage regulators operate on overhead distribution networks to maintain stable line voltage with precise on-load voltage adjustment.

Single Phase Automatic Voltage Regulator On-site Operation Photo

 

Service environment

  • Air temperature: Maximum temperature: +40℃;
  • Minimum temperature: -40℃
  • Humidity: Daily average humidity 100%.
  • Above sea level: Maximum installation altitude: 1000m.
Note: If it needs to be installed in plateau areas with an altitude higher than 1,000 meters, it is essential to consult with the manufacturer to take necessary measures to strengthen insulation during the ordering process. 

Solutions for Voltage Regulator

  • Zanzibar project – voltage regulator selection misalignment with load requirements: root cause analysis & solution
    I. Incident BackgroundThe 33kV line voltage regulator (13 taps, 4% step per tap) supplied by our company for the Zanzibar project has been commissioned and is currently in operation. However, during nighttime periods of low load, the regulator has repeatedly caused the low-voltage side voltage at the downstream factory to rise to 420V, triggering overvoltage shutdowns of production machinery. Following these incidents, the customer specified a maximum permissible low-voltage side tolerance of 41
  • Step Voltage Regulator Solutions for Enhancing Rural Distribution Network Stability and Efficiency
    Ⅰ. Technical Principle and Core Advantages1. Working PrincipleThe 32-step voltage regulator is a tap-switching type voltage regulation device that adjusts voltage by automatically switching the tap positions of series windings:Boost/Buck Mode: A Reversing Switch selects the relative polarity of the series and parallel windings, achieving a ±10% voltage regulation range.32-Step Fine Regulation: Each step adjusts the voltage by 0.625% (32 steps total), preventing abrupt voltage changes and ensurin
  • Innovative Solutions of Step Voltage Regulators in Power Distribution Systems
    1 Executive SummaryVoltage Management Challenges in Modern Distribution Networks: Long-distance feeders causing voltage drop; Distributed energy resource (DER) integration leading to bidirectional power flow; Load fluctuations causing frequent voltage variations.Technical Features of Step Voltage Regulators (SVRs): Employs tap-changing technology to alter transformer winding turns ratio, achieving a ±10% voltage adjustment range (typically in 32 steps, 0.625% per step); Core advantage
  • Comprehensive Solution for Replacing RS Series Stepping Voltage Regulators
    Ⅰ. Analysis of Original Equipment Specifications and System Requirements AssessmentCore Features (ABB RS Series Stepping Voltage Regulator): Voltage Regulation Range: 100V-440V AC input, output 0.7-1.0 times rated voltage (e.g., 400V input yields 280-400V output). Control Interface: Supports 4-20mA analog signal or RS485 digital communication (Modbus protocol), default parameters: 9600 baud rate, no parity, 8 data bits, 1 stop bit. Load Capability: 5A-16A RMS current, suitable for high-power ste
  • Midnight Voltage Surge to 420V Causes Plant Shutdown? The RVR-1 Automatic Voltage Regulator Breaks the
    Introduction: A "Low-Load Hours" Crisis That Struck in the Early MorningBetween 1:00 AM and 7:30 AM on August 24, while most plants were in their low-production overnight window, one facility was forced to shut down three times in succession due to voltage spikes reaching 420V. This was not a grid fault, but a classic case of "off-peak voltage over-limit."During late-night hours when grid load is light, line losses are minimal, and excess reactive power causes the terminal voltage to rise sharpl

Reference Projects for Voltage Regulator

  • Successful Case of 263 Units of 33kV Oil-immersed 32-step Voltage Regulator Controller Project in Bangladesh
    Successful Case of 263 Units of 33kV Oil-immersed 32-step Voltage Regulator Controller Project in Bangladesh01 Overall Project Overview1.1 Project BackgroundIn June 2024, 263 units of 33kV oil-immersed 32-step voltage regulator controller were officially delivered and applied to the Bangladesh Medium Voltage Distribution Network Upgrade Project. R&D and manufactured by Rockwill, these devices are used for voltage stability regulation, load fluctuation adaptation and power supply quality impr

Documentation Resource Library Voltage Regulator

Rockwill Electric Group Profile
Public.
Rockwill Electric Group Profile
Brochure
English
RVR-1 Type  Single Phase Automatic Voltage Regulator  6kV-34.5kV
Restricted.
RVR-1 Type Single Phase Automatic Voltage Regulator 6kV-34.5kV
Operating Instruction
English
PDF
PDF
RVR-1  Single Phase Automatic Voltage Regulator 6kV-34.5kV
Restricted.
RVR-1 Single Phase Automatic Voltage Regulator 6kV-34.5kV
Catalogue
English
PDF
PDF

Certifications Voltage Regulator

FAQ for Voltage Regulator

What is the regulation range and step accuracy of the RVR-1 Step Voltage Regulator?

 Designed as a tap-changing autotransformer compliant with IEEE C57.12, the RVR-1 Step Voltage Regulator delivers precise voltage correction across a full ±10% boost and buck range in 32 loaded steps, with each step providing approximately 0.625% voltage adjustment.

What international grid standards and frequencies does the RVR-1 Step Voltage Regulator support?

The RVR-1 Step Voltage Regulator fully complies with IEEE C57.12 standards and operates seamlessly on both 50Hz and 60Hz global power grids, covering system voltage classes from 2,400V (60kV BIL) up to 34,500V (200kV BIL).

How does the RVR-1 Step Voltage Regulator adapt to different line voltage grades?

All units of the RVR-1 Step Voltage Regulator are equipped with internal potential winding taps and an external ratio correction transformer, enabling a single regulator unit to flexibly adapt to multiple system voltage levels without replacement.

What mounting and installation options are available for the RVR-1 Step Voltage Regulator?

The RVR-1 Step Voltage Regulator provides two field installation configurations: smaller kVA models feature pole-mount support lugs and anchoring fittings for overhead pole or platform installation, while large-capacity units include integrated heavy-duty substation bases for pad-mounted ground deployment.

Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Message
Inquiry
Email
E-mail
WhatsApp
WhatsApp
Chat
Chen/CEO