| Brand | ROCKWILL |
| Model NO. | Original Manufacturer Dead-Tank SF6 Circuit Breaker-170kV |
| Rated voltage | 170kV |
| Rated normal current | 5000A |
| Rated frequency | 50/60Hz |
| Rated short circuit breaking current | 50kA |
| Series | RHD |
Rockwill Group is a leading high-tech enterprise in China, specializing in the R&D, manufacturing, and sales of medium- and high-voltage switchgear and components for over 20 years. Following Pinggao Electric, XD Group, and XJ Electric, Rockwill Group is one of the few domestic manufacturers in China that has independently mastered the core technology of 170kV SF₆-free dead tank circuit breakers and successfully commercialized the product.


| Parameter | Value |
|---|---|
| Rated maximum voltage | 170 kV |
| Rated maximum current | 2500~5000 A |
| Rated frequency | 50/60 Hz |
| Lightning impulse withstand voltage | 750/860 kV |
| Rated short-circuit breaking current | 31.5~50 kA |
| Rated peak withstand current | 80~125 kA |
| Creepage distance | 25~31 mm/kV |
| Partial discharge | ≤10 pC |
| Opening time | ≤30ms |
| Alarm/blocking pressure | 0.55/0.50 MPa |
| Gas moisture content | ≤150 ppm(v) |
| Heater voltage | AC220 V |
| Voltage of energy-store motor | DC110/220 V |
| 1min Power frequency withstand voltage | 325/365 kV |
| First open pole factor | 1.5 |
| Rated short-circuit duration | 3 s |
| Rated cable/line charging breaking current | 160~250 A |
| Rated making current (peak) | 100~125 kA |
| Operation sequence | O-0.3s-CO-180s-CO |
| Breaking time | ≤60 ms |
| Closing time | ≤100 ms |
| Rated SF₆ gas pressure | 0.6~0.7 MPa |
| SF₆ annual gas leakage rate | ≤0.5% |
| Mechanical life | 10000 times |
| Voltage of control circuit | DC110/220 |
| Applied standards | GB/T 1984-2024、 IEC 62271-100 |

Service environmentUltra-low gas leakage rate < 0.1% per year, with long service intervals, cutting long-term operational workload to zero.
Yes. Oil-free spring-operated structure delivers stable performance, low noise, and high reliability. No oil means no oil-related maintenance.
Built-in current transformers (up to 15) for measurement and protection, integrated voltage dividers, and standardized module interfaces for flexible combinations.