| Brand | ROCKWILL |
| Series | RHB |
| Rated voltage | 72.5kV/126kV/145kV/252kV |
| Rated current | 3150/4000/5000A |
| Rated peak withstand current | up to 158 kA |
| Rated short-time withstand current up to | up to 63 kA |
| Rated frequency | 50/60Hz |

Premium dynamic sealing with Glyd-ring & step-type seal, lowering startup friction and eliminating gas leakage effectively.
Imported stable control valve equipped with anti-slow-opening protection against abnormal gas pressure drop.
Hydraulic operating mechanism fitted with dual independent trip circuits plus double relay protection to improve operational reliability.
Self-blast arc extinguishing design, available in single or three-phase post porcelain insulator construction.
Pointer-type density monitor fitted for real-time SF6 gas pressure and density supervision.
| Specifications | Unit | Value | ||||
|---|---|---|---|---|---|---|
| Rated voltage | kV | 72.5 | 126 | 145 | 252 | |
| Rated current | A | 3150/4000/5000 | ||||
| Rated frequency | Hz | 50/60 | ||||
| Rated short-time withstand current up to 3 s | kA | up to 63 | ||||
| Rated peak withstand current | kA | up to 158 | ||||
| 1 min power frequency withstand voltage (r.m.s) | To earth/Between phases | kV | 140 | 230 | 275 | 460 |
| Across isolating distance | kV | 160 | 300 | 315 | 530 | |
| Lightning impulse withstand voltage (peak) | To earth/Between phases | kV | 325 | 550 | 650 | 1050 |
| Across isolating distance | kV | 375 | 650 | 750 | 1200 | |
| Rated SF6 gas pressure (20℃) | MPa | 0.5 | 0.5 | 0.5 | 0.6 | |
| Rated SF6 annual leakage | % | ≤0.5 | ||||
Note:Beyond the standard specifications listed, we offer deep customization for voltage levels and insulation levels to meet specific project requirements (e.g., high altitude or heavy pollution adaptation). All non-standard solutions are designed in strict accordance with IEC/GB standards, ensuring superior electrical performance and safety margins while meeting personalized parameters.
RHB-72.5

RHB-123/145

RHB-245

Ambient temperature: -30°C~+40°C
Altitude <1000m Wind speed: <34m/s
Daily temperature difference: <25°C
Solar irradiance: < 0.1W/cm²
Monthly average relative humidity: <90%
Ice - coating thickness: <10mm
Seismic acceleration resistance: Horizontal <0.2g, vertical <0.1g Installation location: Outdoor
Transmission Line and Transmission Equipment Protection
Industrial and Mining Power Systems
Power Grid in High‑Altitude Areas
Smart Distribution Network and Automated Operation
The advanced self-blast interruption principle utilizes the thermal energy of the arc itself for extinction, which reduces the operating energy required from the mechanism.
This leads to lower mechanical wear and tear over time. Combined with our premium sealing technology that minimizes SF6 leakage (≤0.5% annually), the RHB series offers a highly cost-effective solution with reduced maintenance needs, fully supported by a 20-year warranty.
Yes. While our standard service environment covers temperatures from -30°C to +40°C and altitudes under 1000m, we specialize in customization. For projects in high-altitude or heavy pollution zones (like coastal salt mist areas), we can adjust insulation levels and sealing materials to ensure reliable performance beyond standard limits.
Safety is paramount. The breaker is equipped with an imported stable control valve that features specific "anti-slow-opening" protection. If abnormal gas pressure drops are detected, this mechanism prevents the breaker from operating slowly (which could damage contacts), thereby protecting the equipment integrity and preventing accident escalation.
Absolutely. We understand that EPC contractors and renewable energy stations often have unique interface or dimension requirements. Beyond our standard 72.5kV-252kV range, we offer deep customization for voltage levels and insulation parameters, all backed by comprehensive type test reports to meet international bidding standards.